E3M071 Line module ”Interactive” (supersedes E3M070)
87
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
20.3 Special
functions
Emergency operation
–
Alarm evaluation upon ”Emergency operation” via
Emergency operation proc-
essor
and ”Emergency operation” in the detector
–
Upon emergency alarm, control console B3Q... gives a ”combined alarm”
with
flashing response indicator at the detector
–
Upon line short circuit
and
failure of the line processor there is
no
”Emergency
alarm”
–
Mimic display output (connectors ST10) only active with emergency alarm
Line separator
Upon short circuit the part of the line which malfunctions must be separated from
the rest of the line. This is carried out by line separators integrated in the detectors,
manual call points and input/output modules (however, there are detectors without
integrated separator).
A line separator is always integrated in the manual call points and input/output mo-
dules.
According to EN54 a ”simple error” can cause the malfunction of up to 32 detectors
(i.e. install a line separator at least after every 32 detectors).