E3G080 Control module ”Extinguishing”
158
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
37.10 Connections
Extinguishing activated
Main valve
(undelayed)
0V
Stop- or blocking button
Sector valve
(delayed)
E3G080
1
2
3
4
5
6
7
8
9
10
11
12
+
-
+
+
-
+
-
13
14
15
16
17
18
19
20
A
B
F11
can be calibrated 16...320
Ω
(connect to
chassis ground)
Module chassis ground
Terminal block
X10
F13
Alarm horn monitored
steady / pulsating
Illuminated warning panel
monitored
(steady / pulsating)
Manual activation
Loss of extinguishing agent
F14
F16
0V
Exting. blocked / Emergency stop
0V
0V
Extinguishing control console
B3Q440 (LON interface)
Interlocking with other E3G080
24V max. 2A
4k75
max. 150
Ω
2)
3)
3)
3)
ST22
ST21
ST11
ST12
ST13
B3Q440
24V from the control unit
(E3X10. / AlgoPilot ’K7’)
+
Ground
-
to other E3G080
max. 600m
1k2
1k2
1k2
24V max. 2A
R151
2
3
4
+
+
Plug-in terminals
K1
Supply for
I-Bus modules
to other I-Bus modules
from previous I-Bus modules
1
blue
blue
green
red
24V
5V
Double flat cable header
ST1
Data communication
I-Bus modules
to other I-Bus modules
from previous I-Bus modules
Z5.6V
1k2
Z5.6V
2)
4)
F7
GND
-
-
5)
4k75
Horn universal
4k75
24V max. 2A
24V max. 2A
6)
1,2,3
5
12
4k75
AGO 24.1 Ex
4k75
13
4
6,7
AGE24
4+
5-
6+
7-
1,2
5.6
3.4
4k75
AGN24.5
4k75
6)
illuminated
warning panel
only valid to EP5
1)
1)
6)
4k75
AGN24.5 or horn universal
4k75
1)
1)
illuminated warning panel
illuminated
warning panel
illuminated
warning panel
can be calibrated 16...320
Ω
4k75
4k75
4k75
4k75
max. 150
Ω
max. 150
Ω
26 P
in
26
P
in
Notes:
1) The polarity indicated at terminals 4...7 applies to active status.
2) Instead of the alarm resistor (1k2) A Z diode (5.6 V) can also be inserted for the stop/blocking button.
3) Choice of make or break contact. Zener diodes forbidden!
4) Max. 600m between E3G080 and one B3Q440 with a wire gauge of 0.8mm (twisted);
- with several B3Q440 on the same stub line, correspondingly shorter,
- the deciding factor is the maximum current per B3Q440,
- in the supply line to the last B3Q440, a voltage drop of max. 6 V is permissible.
5) If control lines / detection lines are not used, a termination resistor need not be connected.
6)
only valid for EP5:
For change of tone, depending on alarm horn, use either the positive pole of the "Illuminated warning panel" output,
or intermediate relay