Siemens BC-35 Installation Manuallines Download Page 3

Replace the batteries if the results of 

b, c, 

or 

above are

not acceptable.

Step   2

Verify that the BC-35 is providing a charging current.

a. If an MM-35 is being used in conjunction with a BC-35,

check the meter and verify that a current is being
supplied to the batteries either in a constant or a
pulsed mode.

b. If no MM-35 is being used, place an analog VOM meter

with a 10 amp scale in series with the batteries con-
nected to the BC-35 module. If the batteries are being
charged, the VOM meter will indicate a constant
current or pulsed current is being provided to the
batteries.

A constant charging current or pulsed charging current
is displayed if the battery voltage is between 18.3 VDC
and 27.7 VDC. Once the battery is fully charged, a
pulsed charging current is present on a periodic basis.
The time between pulses is determined by the rate of
discharge due to the internal circuitry of the charger
and the ability of the individual battery to accept and
maintain the charge condition. The constant charge
current is between .5 and 1.5 amps for the BC-35 and
increases proportionally if BE-35 modules are used.

On initial system startup, when the battery charger is
functional, but the battery trouble indicator remains on,
the batteries may not have had time to properly
charge—as much as 24 hours may be necessary for
charging. After charging for 24 hours with the charging
current as described above, and the BC-35 trouble
signal still on:

Summary of Contents for BC-35

Page 1: ...roprietary The BC 35 charging circuit provides a charging current only if the voltage of the batteries being used is between 18 3 VDC and 27 7 VDC If the battery voltage is out of this range the BC 35 will automatically cut off its charging circuit CAUTION Disconnect the system power input before installing the BC 35 and or BE 35 cable connections The BC 35 module has a trouble signal for both hig...

Page 2: ... and 2 below Step 2 may also be used to troubleshoot the BC 35 when a trouble condition is indicated Step 1 Test the batteries connected to the BC 35 module a Remove the battery leads b Test the open battery voltage it should be between 22 and 27 VDC c Reconnect the battery and test it under a load con dition If possible remove the AC power from the system and measure the battery voltage Activate ...

Page 3: ...arging current is displayed if the battery voltage is between 18 3 VDC and 27 7 VDC Once the battery is fully charged a pulsed charging current is present on a periodic basis The time between pulses is determined by the rate of discharge due to the internal circuitry of the charger and the ability of the individual battery to accept and maintain the charge condition The constant charge current is ...

Page 4: ...f the power supply If there are no volts at this point replace the BC 35 module If there are more than 2 VDC at this point and no alarm is present replace the CP 35 panel This information is provided to assist you in diagnosing relatively routine problems There may be extenuating circumstances involved which are not covered here If further assistance is needed please contact your Regional Engineer...

Reviews: