Smart Infrastructure 

 

CC1N7562en 

 

 

12/20/2019 

Notes on product liability 

 

AZL66 units may only be used in building services plant and only in compliance 
with the applications described in this document. 

 

Compliance with all requirements described in the following chapters is a 
mandatory condition for using the AZL66. 

 

Local safety regulations (installation, etc.) must be complied with. 

 

It is not permitted to open AZL66 units. The warranty obligation shall become void 
if this requirement is violated. 

 

 

Caution 

 
It is not permitted to open, interfere with, or modify the AZL66. 
 

  All activities (mounting, installation, service work, etc.) must be performed by 

qualified staff 

 

Before carrying out any wiring changes in the connection area, isolate the plant 
from the power supply (all-pole disconnection). Ensure that the plant cannot be 
inadvertently switched on again and that it is indeed dead. Failure to observe this 
information poses a risk of electric shock 

 

Take suitable measures to provide protection against accidental contact at the 
electrical connections. Failure to observe this information poses a risk of electric 
shock 

 

On completion of every task (mounting, installation, service work, shutdown, etc.) 
always check that the CAN interface is wired and connected correctly (RAST3.81 
jack) in the AZL66 housing and that the parameter settings have been made 
correctly. Failure to observe this information poses a risk of damaging the safety 
functions and a risk of electric shock 

 

These AZL66 units must not be put into operation following impact or shock; even if 
they do not exhibit any visible damage, their safety functions may be impaired. 
Failure to observe this information poses a risk of damaging the safety functions 
and a risk of electric shock 

 

The burner or boiler manufacturer must ensure degree of protection IP40 / IP54 for 
the LMV6 and AZL66 as per DIN EN 60529. Failure to observe this information 
poses a risk of damaging the safety functions and a risk of electric shock 

 

 

Siemens does not assume responsibility for damage resulting from unauthorized 
interventions. 
 
Electromagnetic emissions must be checked on an application-specific basis! 

 
Only 

qualified personnel

 are allowed to start up and operate the AZL66. Qualified 

personnel in the context of the safety-related notes contained in this data sheet are 
persons who are authorized to commission, ground, and tag units, systems, and 
electrical circuits in compliance with established safety practices and standards. 
 

Note the following: 

 
The AZL66 may only be used for the applications described in the technical 
documentation and only in connection with Siemens burner management systems. 
 
The AZL66 can only function correctly and safely if shipped, stored, set up, and 
installed correctly, and operated and maintained with care. 
 

 

Qualified personnel 

Correct use 

Summary of Contents for AZL66 Series

Page 1: ... the burner s immediate vicinity AZL66 units are used for the display operation and parameterization of specific safety related and non safety related burner functions Key plant data and fault codes can be queried and displayed Communication between the AZL66 and the LMV6 takes place via the CAN interface The AZL66 and this data sheet are intended for original equipment manufacturers OEMs using th...

Page 2: ...itional buttons Many languages possible With USB port With LED to visualize the status of the burner Back lit LCD support dependent on LMV6 Fault display via an LED Backup function Housing designed for panel cut out mounting IP54 degree of protection when installed Supplementary documentation Product type Type of documentation Documentation number LMV60 110A2 User Documentation A7560 1 Data Sheet ...

Page 3: ...that the parameter settings have been made correctly Failure to observe this information poses a risk of damaging the safety functions and a risk of electric shock These AZL66 units must not be put into operation following impact or shock even if they do not exhibit any visible damage their safety functions may be impaired Failure to observe this information poses a risk of damaging the safety fun...

Page 4: ...ersunk cross head screws in the housing do not apply excess pressure Note If the AZL66 does not fit inside the designated opening check the cut out and the housing The AZL66 units are manufactured with installation dimensions of 90 1 x 125 7 mm 0 5 The dimensions of the front panel result in a grid dimension of 90 5 mm The mounting mechanisms enable the ALZ66 units to be installed in front panels ...

Page 5: ...nction None Rotary knob TURN Navigate through tile views or list views Can be turned clockwise to the right or down Can be turned counterclockwise to the left or up Change parameter values None Rotary knob ENTER Select a tile menu item Confirm a change to a parameter value Acknowledge messages Back Return Exit a tile menu item value adjuster without making further changes Menu Jump to the top leve...

Page 6: ...aptation of the LMV6 to its components accessories Central repository of all relevant parameters for commissioning Maintenance prompt message Maintenance is carried out at regular intervals by trained specialist personnel The most important information required by the heating engineer to carry out maintenance is stored here Repository for error and fault history Entering the password Changing the ...

Page 7: ...the AGG6 635 signal cable has been connected to the AZL66 correctly The AZL66 must be used in a dry and clean environment The electrical power supply must be disconnected prior to installation The requirements of protection class II must be observed for the wiring Static charges must be avoided since they can damage the electronic components of the AZL66 on contact Recommendation Use ESD equipment...

Page 8: ... and guidelines Standards and certificates Note Only in connection with the LMV6 ISO 9001 2015 ISO 14001 2015 OHSAS 18001 2007 China RoHS Hazardous substances table http www siemens com download A6V10883536 Disposal notes The AZL66 contains electrical and electronic components and must not be disposed of together with domestic waste Local and currently valid legislation must be complied with Prere...

Page 9: ... as part of a reverse engineering process for debugging purposes to the extent that these are linked to libraries licensed under the GNU Lesser General Public License You are not permitted to distribute information resulting from this reverse engineering process of from the modified proprietary components Your rights to modify proprietary components originating from parties other than Siemens are ...

Page 10: ...9 H301 A100 Functions Graphic display 4 3 TFT with 480 x 272 pixels Parameter setting functions and display functions Saving of fault histories and error histories Reset Burner rapid shutdown using button combinations 3 access levels 2 of which have password protection Parameter backup function ...

Page 11: ...g to UL94 V0 PC ABS Weight Approx 260 g Pollution degree 2 Tightening torque for fixing screws Max 0 5 Nm Cut out dimensions 90 1 x 125 7 mm 0 5 Signal cable White in color Shielded With RAST3 81 connector Cable length 3 m Place of installation Under the burner hood arrangements for SKII EN 60730 1 additionally required Connection Color Wire cross section in mm 24 V DC 1 White 0 5 24 V DC 2 Brown ...

Page 12: ...anical conditions Class 2M2 Temperature range 20 to 60 C Humidity 95 r h Operation DIN EN 60721 3 3 Climatic conditions Class 3K3 Mechanical conditions Class 3M3 Temperature range 20 to 60 C Humidity 95 r h Installation altitude Max 2 000 m above sea level Warning Condensation formation of ice and ingress of water are not permitted Failure to observe this information poses a risk of damaging the s...

Page 13: ...13 14 Smart Infrastructure CC1N7562en 12 20 2019 Connection diagram Example Basic diagram of AZL66 with LMV6 Connection AZL66 to LMV6 ...

Page 14: ...rastructure CC1N7562en 12 20 2019 Dimensions Dimensions in mm 119 2 90 1 143 2 125 7 140 46 1 22 1 M1 2 7560m07 0319 AZL66 2019 Siemens AG Smart Infrastructure Berliner Ring 23 76437 Rastatt Germany Subject to change ...