5.  After removing the circuit board assembly 

from the housing, turn the housing over and 
mark the display with the permanent marker. 
This marking will be helpful in distinguishing 
the new the new display from the old one. 

6.  Use your thumb and index finger to gently lift 

the retaining device where the display ribbon 
cable connects to the circuit board. 

 

Figure 4.  Ribbon Cable Attachment Point.

 

7.  Gently remove the ribbon cable from the 

receptacle on the terminal board. 

8.  Turn the circuit board over and use needle 

nose pliers to loosen the display by carefully 
squeezing the three attachment prongs 
while gently pushing them toward the board 
surface. 

 

Figure 5.  Display Module Attachment Prongs.

 

9.  After the attachment prongs are loosened, 

the display can be lifted from the board. Use 
a flat-blade screwdriver to gently pry it loose. 

Installing the New Display Module 

Press the new display assembly into the circuit 
board on the side opposite the RJ-11 port or 
terminal blocks. 

1.  Insert the ribbon cable into the receptacle 

and secure the retainer by gently pushing it 
down on both sides. 

2.  Insert the circuit board into the front housing. 

Ensure that the board is properly seated in 
the retaining tabs. 

3.  Connect the RJ-11 cable or re-attach the 

sensor wiring (see notes or pictures taken in 

Removing the Old Display Module

Step 3. a). 

4.  Install the sensor on the sensor base and 

turn the retaining screw counterclockwise 
until properly engaged with sensor housing. 

5.  To maximize the life of the OLED, it is 

recommended that the screen saver 
functionality be enabled at the sensor. For 
details, see one of the following HMI guides: 

 

For sensors with an RJ-11 port, see 

Room Unit for TEC, and ATEC Operator 
Interface Guide

 (125-703). 

 

For sensors without an RJ-11 port, see 

Series 2200/2300 Room Units for 
Primary Equipment Controllers Operator 
Interface Guide

 (125-706). 

The installation is now complete. 

 

 