GAMMA instabus

Technical Product Information

February 2019

Weather Station (GPS) AP 257/22

5WG1 257-3AB22

Siemens Switzerland Ltd

DS01

Update: http://www.siemens.de/gamma-td

Building Technologies Division
International Headquarters

 Siemens AG 2019

Theilerstrasse 1a

Subject to change

CH-6300 Zug

2

Installation Instructions

If the weather station has been damaged, it must not be
commissioned.

V

WARNING

The device must be mounted and commissioned by an
authorised electrician.

For planning and construction of electric installations,
the relevant guidelines, regulations and standards of
the respective country are to be considered.

Technical Specifications

Sensors

Wind sensor:
Measuring range: 0 ... 35 m/s,
Resolution: 0.1 m/s
precision at ambient temperature -20…+50°C:
±22% of measured value with air flow from 45…315°
±15% of measured value with air flow from 90…270°
(air flow onto the front equals 180°)

Brightness sensor:
Measuring range:   0 ... 150.000 lux,

 Resolution at:

0 ... 120 lux

   1 

lux

121 ... 1.046 lux   

2 lux

1.047 ... 52.363 lux   63 lux
52.364 ... 150.000 lux 423 lux

Precision:

±20% at 0 lx … 10 klx
±15% at 10 klx … 150 klx

Temperature sensor:
Measuring range: -30 ... +50 °C,
Resolution:

 0.1 °C

Precision:

±0,5°C at +10…+50°C,
    ±1°C at -10…+10°C,
 ±1,5°C at -25…-10°C

Rain sensor:
Heating: approx. 1.2 W

Voltage supply

Bus voltage: via the bus line

KNX bus current: 9 mA

Auxiliary power sensor electronics:
AC 20 V (AC 12...28V) 50/60 Hz or
DC 24 V (DC 12...40V) max. 185 mA at DC 12V, residu-
al ripple < 10%, max. permissible cable length 100 m

Power consumption: max. 2.3 VA

Operator elements
1 commissioning button: for switching over between
normal mode / addressing mode

Display elements

1 red LED: for display of normal mode / addressing
mode (off / on)

1 red LED: as control display for GPS reception

Connections

Voltage supply: plug terminals for solid conductors or
finely stranded conductors 0.5 ... 1.5mm²

Bus connection: screwless bus terminal,
0.6... 0.8 mm

 single-wire, insulation strip length 5

mm.

Mechanical data

housing: plastic

Dimensions :
approx. 118 mm x 96 mm x 77 mm (L x W x H)

Weight: approx. 170 g

Fire load: approx. 5360 kJ

Mounting: Mast or wall mounting

Electrical safety

Degree of pollution (according to IEC 60664-1): 2

Type of protection (according to EN 60529): IP 44

Overvoltage category (according to IEC 60664-1): III

Bus: safety extra-low voltage (SELV) DC 24 V

Device complies with EN 50090-2-2

EMC requirements
complies with EN 50090-2-2

Environmental conditions

Climatic conditions: EN 50090-2-2

Ambient temperature operating: - 30 ... + 50

°

C

Ambient temperature non-op.: - 30 ... + 70

°

 C

Relative humidity (non-condensing): 5 % … 93 %

Markings
KNX EIB

CE mark
complies with the EMC regulations (residential and func-
tional buildings), and low voltage regulations

Summary of Contents for AP 257/22

Page 1: ... is not lowered completely but only so far that the sun can still shine into the room for a certain distance e g 50 cm which can be set by a parameter This way the occupant of the room can look outside in the lower part of the window and plants on the windowsill can receive sunshine With externally mounted Venetian blinds the sun track ing control of slats can avoid heat influx into the room due t...

Page 2: ...ing approx 1 2 W Voltage supply Bus voltage via the bus line KNX bus current 9 mA Auxiliary power sensor electronics AC 20 V AC 12 28V 50 60 Hz or DC 24 V DC 12 40V max 185 mA at DC 12V residu al ripple 10 max permissible cable length 100 m Power consumption max 2 3 VA Operator elements 1 commissioning button for switching over between normal mode addressing mode Display elements 1 red LED for dis...

Page 3: ...h water could con tinue to drop on to the precipitation sensor even after rain or snow has stopped The weather station should not be shaded by the building or e g trees There must be at least 60 cm free space around the weather station to allow correct wind measurements and to prevent the station from being snowed in It is recommended to install the weather station on a mast It should be en sured ...

Page 4: ...a mast pole Fasten the holder vertically with the curved side to the mast pole and the bar to the bottom see fig 6 Figure 6 View of the rear wall and drilling scheme Dimensioning of the rear of the enclosure with holder see fig 7 drilling scheme see fig 8 Figure 7 Figure 8 Preparing the weather station The lid of the weather station with the rain sensor is slotted in on the right and the left at t...

Page 5: ...ke care that the connections are correctly made A wrong connection can destroy the electronics of the weather station During assembly care should be taken that the tempera ture sensor small circuit board on the lower part of the enclosure is not damaged The cable connection be tween the circuit board and the rain sensor may not be torn off or bent while making the connection The wind measurement v...