11
Figure 8
Positioning the Alarm LED
1. When installing FD-UL detectors in a FireFinder XLS panel,
use the following panel versions
•
PMI ver 10.02 or later
•
Zeus ver 10.02 or later
•
DLC ver 06.01
or later
2. When the audible base ABHW-4BZ works with FD-UL series
detectors. Up to 6 tone patterns and 2 volume levels can be
selected by user with system configuration tool; there are
two power types for ABHW-4BZ during alarm, “Loop
Powered” and “External Powered” which can be configured
by system tool.
3. When the audible base ABHW-4BZ works with H-series
detector Only “External Powered” can be used. A fixed 85dB
tone is provided and only 2 tones can be selected (steady
and Temporal 3, refer to Figure 6): Steady: without a jumper
at terminals 3 and 4; Temporal 3: terminals 3 and 4 are
shorted with jumper.
4. When use “External Powered” for alarm, the ABHW-4BZ still
takes some power from loop during both supervision and
alarm status to keep it alive and external power is only for
the alarm current.
5.
For additional information on the modules used in an
individual system, refer to the Installation Instructions for that
particular module or contact your authorized Siemens
Industry, Inc. representative.
BASE
MOUNTING
HOLES
ALARM LED LOCATION
WITH DETECTOR
INSTALLED IN BASE