9
Building Technologies
007026_s_en_--
Fire Systems
2018-06-15
Technical data
Supply
FDS221-R, FDS221-W
FDSB291
FDSB292
Operating voltage
DC 12…33 V
DC 12…33 V
Operating current (quiescent)
Sound activated
Max. 250 µA
3.5 mA
Max. 150 µA
1.2 mA
Sounds
11
2 alarm levels
3 sound levels
11
2 alarm levels
2 sound levels
1
1 alarm level
1 sound level
Sound level
80…99 dB(A)
80…88 dB(A)
84 dB(A)
Ext. Alarm indicator (AI)
2
1
Operating temperature
-25…+70 °C
-25…+70 °C
(observe point detector data)
Storage temperature
-30…+75 °C
-30…+75 °C
Air humidity
95 % rel.
95 % rel.
Communication protocol
FDnet
FDnet
Collective
Conductor cross-section on
detector base
According to detector base
0.2…1.5 mm
2
Color
~RAL 3000 flame red
~RAL 9010, pure white
~RAL 9010, pure white
Protection category (IEC 60529)
with
Base FDB221 or FDB222
Base attachment FDB291
Base FDB221 and sealing
element FDBZ295
Base attachment humid
FDB293, base attachment wet
FDB295
Wall mounting with feed line
from below IP43, otherwise IP40
IP44
IP54
IP43
-
-
-
-
Standards
EN 54-3, EN 54-17
EN 54-3
Approvals
VdS
LPCB
FM
DNV GL (marine)
G204073
531p
3029351
MEDB00003UV
G204062
531u
3029351
MEDB00003UV
System compatibility FDnet
FS20, AlgoRex, SIGMASYS
FS20, AlgoRex,
SIGMASYS
-