Installation | 7
73/174
500-8384.9 • Version 11 • Installation and Operating Instructions • 8DJH
Tab. 41:
Fixing points for panels without cable feeder
Panel width 310 / 430 / 500 mm
14x28
▪ Type S
▪ Type H
▪ Type V
▪ Type M(430) / (500)
▪ Type E / E(500)
7.15 Joining the panels
INFORMATION
To interconnect panels, there must be a sufficient distance between the wall and the panel to
be lined up.
⇨ Keep the necessary wall distances [
Page 55, "Preparing the switchgear room"].
Preparing the existing switchgear
If an existing switchgear assembly shall be extended with panels or panel blocks, the
corresponding end panel must be prepared.
Removing the busbar termination:
1. Remove the busbar termination cover
1
.
2. Remove 3 clamping covers for dummy plugs
2
and silicone dummy plugs
3
.
Fig. 67:
Removing the busbar termination
3. Remove cap, sealing stoppers or bolt-and-washer assemblies from the side wall: