Technical data | 4
35/174
500-8384.9 • Version 11 • Installation and Operating Instructions • 8DJH
Degrees of protection
The panels fulfill the following degrees of protection according to IEC 62271-200, IEC 60529 and
DIN VDE 0671-200:
▪ IP2X (standard) for parts under high voltage
–
for air-insulated metering panels
–
for panels with HV HRC fuses
▪ IP3X (option) for the switchgear enclosure of the operating front and the side walls
▪ IP3X (standard, option: IP4X) for low-voltage compartments
▪ IP65 for parts under high voltage
–
for panels without HV HRC fuses
–
for switchgear without air-insulated metering panels
Transport regulations
According to "Annex A of the European Agreement Concerning the International Carriage of
Dangerous Goods by Road (ADR)" launched on September 30, 1957, Siemens gas-insulated
medium-voltage switchgear does not belong to the category of dangerous goods in respect of
transportation, and is exempted from special transport regulations according to ADR,
Clause 1.1.3.1 b).
4.8 Dimensions and weights
The switchgear weight depends on the switchgear design and the degree to which it is
equipped. The table shows mean values.
Tab. 31:
Weight of individual panels
Panel type
Width
Gross weight for a switchgear height of
Low-voltage
compartment
[mm]
1200 mm
1400 mm
1700 mm
600 mm
approx. [kg]
approx. [kg]
approx. [kg]
approx. [kg]
R
310
100
110
120
40
R(500)
500
140
150
170
60
K
310
100
110
120
40
K(E)
430
130
140
160
50
T
430
135
145
160
50
L
430
130
140
155
50
L (type 1.1) without
4MT3
500
210
220
240
60
L (type 2)
500
160
170
190
60
M(SK/SS/KS)
840
-
370
400
70
M(KK)
840
-
270
300
70
M(500) incl. 3x4MT3
500
230
240
260
60
S
430
130
140
160
50
S(500)
500
150
160
180
60
S(620)
620
200
220
240
45
H
430
135
145
160
50
V
500
240
250
270
60
E
310
100
110
120
40
E(500)
500
140
150
170
60
Summary of Contents for 8DJH