Operation | 9
139/174
500-8384.9 • Version 11 • Installation and Operating Instructions • 8DJH
Panel type
Operation
L1.1
Circuit-breaker panel type 1.1
Page 150, "Operating the panel with cir-
L2
Circuit-breaker panel type 2
Page 146, "Operating the panel with cir-
V
Bus sectionalizer panel with circuit-breaker
9.4 Operating the panel with switch-disconnector
This chapter describes the manual operation of the following panel types:
▪ Panels with three-position switch-disconnector (panel types R and S)
▪ Panels of the panel type M(500)
The operations are exemplarily shown for a ring-main feeder (panel type R).
Motor operating mechanism (option)
The panels can be equipped with a motor operating mechanism for all switching operations. The
use of the motor operating mechanism is described in the circuit documentation.
Manual switching operations are also possible with motor operating mechanism. If the locking
device is operated in order to perform a switching operation, electrical switching commands are
suppressed.
INFORMATION
If the auxiliary power supply is interrupted while the motor is charging the operating spring,
the operating mechanism returns to the initial situation autonomously.
To repeat the switching operation, switch the auxiliary voltage on again.
Control board for switch-disconnector (example)
R
1
Ready-for-service indicator
2
Actuating opening for switch-disconnector
3
Locking device (option for spring-operated
mechanism)
4
Padlock (option)
5
Actuating opening for earthing switch
6
Position indicator for earthing switch
7
Position indicator for switch-disconnector
9.4.1 Switching the three-position switch-disconnector from OPEN to CLOSED
position
☒ Three-position switch-disconnector in OPEN position
1. Check service readiness [
2. Remove the padlock (optional) from the locking device.
Summary of Contents for 8DJH
Page 173: ......