![Siemens 7XV5652-0CA00 Manual Download Page 78](http://html.mh-extra.com/html/siemens/7xv5652-0ca00/7xv5652-0ca00_manual_381524078.webp)
Device Data
Auxiliary Voltage V
aux
Rated auxiliary voltage
– Direct voltage
DC 24 V to 250 V
– Alternating voltage
AC 110 V to 230 V/45 Hz to 65 Hz
Permissible voltage range
– Direct voltage
19 V to 300 V
– Alternating voltage
92 V to 286 V
Power consumption
– Direct voltage
Max. 2.2 W
– Alternating voltage
Max. 6.5 VA
Current consumption
– Direct voltage
Max. 120 mA
– Alternating voltage
Max. 60 mA
Operating state display
1 green LED (Power On)
Fuses
Soldered in place
T2.0 A/125 V
Replaceable
T1.6 A/250 V/F1
Protection class
III
Structural Variant
Housing
Metal (industrial housing)
Dimensions
See the dimensional drawings at
Weight
About 450 g
Degree of protection according to EN 60529:
– Housing
IP 41; metal
– Terminals
IP 20
Safety
As per DIN EN 61010 Part 1, overvoltage category
III (AC 3.7 kVA/DC 5.2 kV)
Degree of pollution
2
Fire-resistance rating as per UL 94
V0
5.1
Technical Data
5.1 Device Data
34
Accessories, RS232 Optical Fiber Converter 7XV5652-0CA00, Manual
C53000-G9050-C606-1, Edition 03.2020
Summary of Contents for 7XV5652-0CA00
Page 8: ...8 Zubehör RS232 LWL Konverter 7XV5652 0CA00 Handbuch C53000 G9050 C606 1 Ausgabe 03 2020 ...
Page 12: ...12 Zubehör RS232 LWL Konverter 7XV5652 0CA00 Handbuch C53000 G9050 C606 1 Ausgabe 03 2020 ...
Page 20: ...20 Zubehör RS232 LWL Konverter 7XV5652 0CA00 Handbuch C53000 G9050 C606 1 Ausgabe 03 2020 ...
Page 24: ...24 Zubehör RS232 LWL Konverter 7XV5652 0CA00 Handbuch C53000 G9050 C606 1 Ausgabe 03 2020 ...
Page 40: ...40 Zubehör RS232 LWL Konverter 7XV5652 0CA00 Handbuch C53000 G9050 C606 1 Ausgabe 03 2020 ...
Page 44: ...44 Zubehör RS232 LWL Konverter 7XV5652 0CA00 Handbuch C53000 G9050 C606 1 Ausgabe 03 2020 ...