English
7XT3300-0*A00
44
C53000-B1175-C129-1
EMC tests for noise emission (type tests)
High-Energy Surge Voltages (SURGE),
IEC 61000-4-5 Installation Class 3
- Auxiliary voltage
- Analog measuring inputs, binary inputs
and relay outputs
Pulse: 1.2
μ
s/50
μ
s
Common mode: 2 kV; 12
Ω
; 9
μ
F
Diff. mode: 1 kV; 2
Ω
; 18
μ
F
Common mode: 2 kV; 42
Ω
; 0.5
μ
F
Diff. mode: 1 kV; 42
Ω
; 0.5
μ
F
Line-Conducted HF, Amplitude-modul.
IEC 61000-4-6, Class III
10 V; 150 kHz to 80 MHz; 80 % AM; 1 kHz
Power System Frequency Magnetic Field
IEC 60255-6
IEC 61000-4-8, Class IV
0.5 mT; 50 Hz,
30 A/m; continuous; 300 A/m for 3 s; 50 Hz
Oscillatory Surge Withstand Capability
IEEE Std C37.90.1
2.5 kV (peak value); 1 MHz;
τ
= 15
μ
s;
400 pulses per s; test duration 2 s; R
i
= 200
Ω
Fast Transient Surge Withstand Cap.
IEEE Std C37.90.1
4 kV; 5 ns/50 ns; 5 kHz; burst length = 15 ms;
repetition rate 300 ms; both polarities;
R
i
= 50
Ω
; test duration 1 min
Radiated Electromagnetic Interference
IEEE Std C37.90.2
35 V/m; 80 MHz to 1000 MHz
Damped Oscillations IEC 61000-4-18
2.5 kV (peak value), polarity alternating
100 kHz, 1 MHz,
R
i
= 200
Ω
Standard
EN 61000-6-4 (basic specification)
Radio Noise Voltage to lines, only Power
Supply Voltage IEC-CISPR 11
150 kHz to 30 MHz
Limit value class A
Radio Interference Field Strength
IEC-CISPR 11
30 MHz to 1000 MHz
Limit value class A