Chapter 2) 7XG3124 Application Guide
©2014 Siemens Protection Devices Limited
Chapter 2 Page 34 of 42
Once copied, ensure that any existing 1S24.cid file in the A:/ drive is renamed or deleted (right click on the
file for renaming deletion options).
Then select the copied file in the A:/ drive, right click and ensure it is renamed as 1S24.cid. (Note: The new
.cid file must be renamed “1S24.cid”)
Figure 42: @CHIPTOOL - FTP 2
Rebooting The RA24 With The New 1S24.cid File
A reboot of the RA24 is required once the new 1S24.cid file has been loaded.
The reboot can be done either via powering down and repowering the device or by pressing and holding the
Flag Reset button for about 5 sec until all the LEDs start flashing, refer to Reboot under Monitor Indications.