Chapter 1) 7SR242 Duobias Description Of Operation
©2015 Siemens Protection Devices Limited
Chapter 1 Page 37 of 60
3.8
Current Protection: Under-Current (37, 37G)
Optionally two under-current elements are provided for both line and measured earth current, each can be
selected to either winding 1 or winding 2.
Each phase has an independent level detector and current-timing element.
37-n Setting
sets the pick-up current.
An output is given after elapse of the
37-n Delay
setting.
Operation of the under-current elements can be inhibited from:
Inhibit 37(G)-n
A binary or virtual input.
Gn 37-n U/I Guarded
Operation of the undercurrent guard function.
Inhibit 37(G)-n
A binary or virtual input.
User Inhibit 37(G)-n
Reylogic (graphical logic).
Figure 3-14 Logic Diagram: Undercurrent Detector (37, 37G)