Chapter 3) 7SR242 Duobias Performance Specification
©2015 Siemens Protection Devices Limited
Chapter 3 Page 16 of 50
1.4.2 Emissions
IEC 60255-25
1.4.2.1
Radiated Radio Frequency
Type
Limits at 10 m, Quasi-peak
30 to 230 MHz
40 dB( V/m)
230 to 10000 MHz
47 dB( V/m)
1.4.2.2
Conducted Radio Frequency
Type
Limits
Quasi-peak
Average
0.15 to 0.5 MHz
79 dB( V)
66 dB( V)
0.5 to 30 MHz
73 dB( V)
60 dB( V)
1.4.3 Immunity
1.4.3.1
Auxiliary DC Supply Variation
Quantity
Value
Allowable superimposed ac component
12% of DC voltage
Allowable breaks/dips in supply
(collapse to zero from nominal voltage)
20ms
1.4.3.2
High Frequency Disturbance
IEC 60255-22-1
Type
Level
Variation
Case, Aux Power & I/O common (longitudinal) mode 2.5 kV
10 %
Case, Aux Power & I/O Series (transverse) mode
1.0 kV
RS485 Metallic Comms
1.0kV
No data loss
1.4.3.3
Electrostatic Discharge
IEC 60255-22-2 Class IV
Type
Level
Variation
Contact discharge
8.0 kV
5 %
1.4.3.4
Radiated Immunity
IEC 60255-22-3 Class III
Type
Level
Variation
80 MHz to 1000 MHz
10 V/m
5 %
Summary of Contents for 7SR242 Duobias
Page 1: ...Answers for energy 7SR242 Duobias Transformer Protection Relay Reyrolle Protection Devices ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 6: ...6 www siemens com energy ...
Page 318: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 2 of 64 ...
Page 324: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 8 of 64 ...
Page 358: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 42 of 64 ...
Page 366: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 50 of 64 ...
Page 380: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 64 of 64 ...
Page 381: ......