Default setting
(_:14011:136) V< Threshold
=
90.000 V
Parameter: V< Time delay
•
Default setting
(_:14011:137) V< Time delay
=
0 s
Parameter: I> Blocking
•
Default setting
(_:14011:138) I> Blocking
=
on
Parameter: I> Threshold
•
Default setting
(_:14011:139) I> Threshold
=
150 %
Parameter: I> Time delay
•
Default setting
(_:14011:140) I> Time delay
=
0 s
If the load current exceeds the threshold value
I> Threshold
for the time
I> Time delay
, the overcur-
rent blocking prevents changing to a higher or lower tap. Set the threshold value
I> Threshold
in % in rela-
tion to the rated current. To do this, set the parameter
I reference
for % values.
Parameter: I< Blocking
•
Default setting
(_:14011:141) I< Blocking
=
off
Parameter: I< Threshold
•
Default setting
(_:14011:142) I< Threshold
=
10 %
Parameter: I< Time delay
•
Default setting
(_:14011:143) I< Time delay
=
10 s
If the load current drops below the threshold value
I< Threshold
for the time
I< Time delay
, the under-
current blocking prevents changing to a higher or lower tap. Set the threshold value
I< Threshold
in % in
relation to the rated current. To do this, set the parameter
I reference
for % values.
Blockings for Three-Winding Transformers and Grid Coupling Transformers
Parameter: V< Threshold w1
•
Default setting
(_:136) V< Threshold w1
=
90.000 V
Parameter: V< Threshold w2
•
Default setting
(_:150) V< Threshold w2
=
90.000 V
Settings
Two-Winding Transformer
Addr.
Parameter
C
Setting Options
Default Setting
Ref. for %-values
_:2311:101
General:Rated current
0.20 A to 100000.00 A
1000.00 A
_:2311:102
General:Rated voltage
0.20 kV to 1200.00 kV
400.00 kV
Tap changer
_:13981:111
Tap changer:Maximum
output time
0.02 s to 1800.00 s
1.50 s
_:13981:112
Tap changer:Supervision
behavior
•
off
•
warning
•
alarm block
alarm block
_:13981:113
Tap changer:Motor
supervision time
5 s to 100 s
10 s
_:13981:116
Tap changer:Highest tap
changer pos.
•
Lowest voltage tap
•
Highest voltage tap
Lowest voltage
tap
_:13981:114
Tap changer:Lowest tap
position
-64 to 64
1
8.9.5
Control Functions
8.9 Voltage Controller
1222
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...