SIMEAS-T - Transducer with auxiliary power
22
Transducer with expanded start range and suppressed end range
Example: Transducer with range:
0 to 0.05 to U
EN
≙
0 to 0.8 to A
N
Basic settings
R32: Stop left
R33: Stop right
Break point
Feed U
E
= 0.05 U
EN
± 0.05% U
EN
,
set the output value with trim potentiometer
R51
Set A = 0.8 A
N
± 0.05% A
N
.
Then turn trim potentiometer
R32
to the right until the output value A increases.
Full-scale value
Feed U
E
= U
EN
± 0.05% U
EN
,
set the
output value A = A
N
± 0.05% A
N
with trim potentiometer
R33
.
Transducer with suppressed start range and expanded end range
Example: Transducer with range:
0 to 0.8 to 1.2 U
EN
≙
0 to 0.2 to A
N
Basic settings
R32: Stop left
R33: Stop right
Break point
Feed U
E
= 0.8 U
EN
± 0.05% U
EN
, set
the output value A = 0.2 A
N
± 0.05% A
N
with trim potentiometer
R51
.
Then turn trim potentiometer
R32
to the right until the output value A increases.
Full-scale value
Feed U
E
= 1.2 U
EN
± 0.05% U
EN
, set
the output value A = A
N
± 0.05% A
N
with trim potentiometer
R33
.