6.2 Interface overview
6-159
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
I
2
t pre–warning and motor temperature monitoring
Terminals 5.1 – 5.2: NO contact
open for ”no fault”
Terminals 5.1 – 5.3: NC contact
closed for ”no fault”
Notice
No I
2
t monitoring of the infeed!
You must ensure sufficient power of the infeed module by setting this
parameter accordingly in the configuration.
Terminals 5.
j
must be externally evaluated for the machine responses, for
example, in the PLC. When the motor temperature monitoring responds, the
user/machine manufacturer must define what the response should/must be
S
Reduce the load on the machine
S
Reduce the power
S
Stop
S
Shutdown
If the terminal is not evaluated, and the response that makes sense for this
particular case is initiated in the machine control system, then this can destroy
the system, converter or motor!
The relay is activated if:
S
At NE module
–
Heatsink–temperature monitoring trips
S
At 611D
–
Motor–temperature monitoring trips
–
Heatsink–temperature monitoring trips
–
I
2
t axis limiting responds
S
At 611 universal HRS
–
Motor–temperature monitoring trips
–
Heatsink–temperature monitoring trips
–
I
2
t axis limiting responds
Input current, enable circuits:
Terminals 48, 63, 64, and 65: Input current, optocoupler approx. 12 mA at +24 V
Terminal 663: Input current, optocoupler and start inhibit relay approx. 30 mA at
+24 V
When selecting the switching devices and the auxiliary contact on the main
switch, the contact reliability when switching low currents must be carefully
taken into consideration.
Switching capacity of the signaling contacts:
The max. switching power of the signaling contacts is specified in the interface
overviews of the modules in Chapters 4 and 6, and must be absolutely com-
plied with!
Terminals 5.1, 5.2,
5.3 (X121)
6 Infeed Modules