8.4.2.2
LEDs of the Sirius safety relay
Table 8-2
LEDs of the Sirius safety relay
LED
Operation
POWER
CHANNEL1
CHANNEL2
Line supply
EMERGENCY
STOP
ON
Release circuits
☀
☀
☀
On
Not actuated
Actuated
Closed
☀
○
○
Actuated
Not actuated Open
☀
○
○
Not actuated
Not actuated Open
Fault
☀
○
○
● Relay jammed
● Motor contactor jammed
● Defect in electronics
Open
○
○
○
Cross-circuit/ground fault in EMERGENCY STOP
circuit/no supply voltage
Operation
8.4 Fault and system messages
SINAMICS PERFECT HARMONY GH150 6SL3825
90
Operating Instructions 05/2020