background image

 

 

Digital input module DI 32x24VDC BA (6ES7521-1BL10-0AA0) 

4

 

Manual, 12/2016, A5E32363711-AD 

Preface 

 

 

Purpose of the documentation 

This manual supplements the S7-1500/ET 200MP 

(

https://support.industry.siemens.com/cs/ww/en/view/59191792

) system manual. 

Functions that relate in general to the systems are described in this system manual. 
The information provided in this manual and in the system/function manuals supports you in 

commissioning the systems. 

Changes compared to previous version 

Compared to the previous version, this manual contains the following change: 
Schematic circuit diagram has been updated. 

Conventions 

The term "CPU" is used in this manual both for the CPUs of the S7-1500 automation system 

and for interface modules of the ET 200MP distributed I/O system. 
Please also observe notes marked as follows: 

 

 

Note 
A note contains important information on the product described in the documentation, on the 

handling of the product or on the section of the documentation to which particular attention 

should be paid. 

 

Security information 

Siemens provides products and solutions with industrial security functions that support the 

secure operation of plants, systems, machines and networks. 
In order to protect plants, systems, machines and networks against cyber threats, it is 

necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial 

security concept. Siemens’ products and solutions only form one element of such a concept. 
Customer is responsible to prevent unauthorized access to its plants, systems, machines 

and networks. Systems, machines and components should only be connected to the 

enterprise network or the internet if and to the extent necessary and with appropriate security 

measures (e.g. use of firewalls and network segmentation) in place.  
Additionally, Siemens’ guidance on appropriate security measures should be taken into 

account. For more information about industrial security, please visit 

(

http://www.siemens.com/industrialsecurity

). 

Siemens’ products and solutions undergo continuous development to make them more 

secure. Siemens strongly recommends to apply product updates as soon as available and to 

always use the latest product versions. Use of product versions that are no longer supported, 

and failure to apply latest updates may increase customer’s exposure to cyber threats.  
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS 

Feed under (

http://www.siemens.com/industrialsecurity

). 

Summary of Contents for 6ES7521-1BL00-0AA0

Page 1: ......

Page 2: ..._____________ ___________________ ___________________ SIMATIC S7 1500 ET 200MP Digital input module DI 32x24VDC BA 6ES7521 1BL10 0AA0 Manual 12 2016 A5E32363711 AD Preface Documentation guide 1 Product overview 2 Wiring 3 Address space 4 Diagnostics alarms 5 Technical specifications 6 Dimensional drawing A ...

Page 3: ... only by personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Siemens p...

Page 4: ...he secure operation of plants systems machines and networks In order to protect plants systems machines and networks against cyber threats it is necessary to implement and continuously maintain a holistic state of the art industrial security concept Siemens products and solutions only form one element of such a concept Customer is responsible to prevent unauthorized access to its plants systems ma...

Page 5: ... source software contained in it pursuant to the conditions applicable to the product Siemens accepts no liability for the use of the open source software over and above the intended program sequence or for any faults caused by modifications to the software For legal reasons we are obliged to publish the original text of the license conditions and copyright notices Please read the information rela...

Page 6: ... Table of contents Preface 4 1 Documentation guide 7 2 Product overview 11 2 1 Properties 11 3 Wiring 13 3 1 Wiring and block diagram 13 4 Address space 14 4 1 Address space 14 5 Diagnostics alarms 18 5 1 Status and error displays 18 6 Technical specifications 20 A Dimensional drawing 23 ...

Page 7: ... the specific content you require Basic information The System Manual and Getting Started describe in detail the configuration installation wiring and commissioning of the SIMATIC S7 1500 and ET 200MP systems For CPU 1516pro 2 PN you use the corresponding operating instructions The STEP 7 online help supports you in the configuration and programming Device information Product manuals contain a com...

Page 8: ...ndustry siemens com cs ww en view 86140384 SIMATIC S7 1500 comparison list for programming languages The comparison list contains an overview of which instructions and functions you can use for which controller families You can find the comparison list on the Internet https support industry siemens com cs ww en view 86630375 mySupport With mySupport your personal workspace you make the best out of...

Page 9: ...ion examples support you with various tools and examples for solving your automation tasks Solutions are shown in interplay with multiple components in the system separated from the focus on individual products You will find the application examples on the Internet https support industry siemens com sc ww en sc 2054 TIA Selection Tool With the TIA Selection Tool you can select configure and order ...

Page 10: ...to UTC time to the module Program download to CPU Operating mode switchover RUN STOP Localization of the CPU by means of LED flashing Reading out CPU error information Reading the CPU diagnostic buffer Reset to factory settings Updating the firmware of the CPU and connected modules You can find the SIMATIC Automation Tool on the Internet https support industry siemens com cs ww en view 98161300 PR...

Page 11: ... 0AA0 View of the module Figure 2 1 View of the DI 32x24VDC BA module Properties The module has the following technical properties 32 digital inputs electrically isolated in groups of 16 Rated input voltage 24 VDC Suitable for switches and 2 3 4 wire proximity switches Hardware compatible with digital input module DI 16x24VDC BA 6ES7521 1BH10 0AA0 ...

Page 12: ...gher X Module internal Shared Input MSI V1 0 0 or higher V13 Update 3 or higher PROFINET IO only X PROFINET IO only Configurable submodules sub modules for Shared Device V1 0 0 or higher V13 Update 3 or higher PROFINET IO only X PROFINET IO only You can configure the module with STEP 7 TIA Portal and with a GSD file Accessories The following accessories are supplied with the module and can also be...

Page 13: ...ating a cable shield etc in the Wiring section of the S7 1500 ET 200MP http support automation siemens com WW view en 59191792 system manual Wiring and block diagram The figure below shows you how to wire the module and the assignment of the channels to the addresses input byte a to input byte d Backplane bus interface CHx Channel or channel status LED green M Ground RUN Status display LED green E...

Page 14: ...er different abbreviations module names The following configurations are possible Table 4 1 Configuration options Configuration Short designation module name in the GSD file Configuration software e g with STEP 7 TIA Portal Integrated in hardware catalog STEP 7 TIA Portal GSD file in STEP 7 TIA Portal V12 or higher or STEP 7 V5 5 SP3 or higher 1 x 32 channel without value status DI 32x24VDC BA V13...

Page 15: ...ided into multiple submodules The submodules can be assigned to different IO controllers when the module is used in a shared device Unlike the 1 x 32 channel module configuration each of the four submodules has a freely assignable start address Figure 4 2 Address space for configuration as 4 x 8 channel DI 32x24VDC BA S Address space for configuration as 1 x 32 channel DI 32x24VDC BA MSI The chann...

Page 16: ...olved For the 1st submodule basic submodule the value status is not relevant For the 2nd to 4th submodule MSI submodule the value status 0 indicates that the value is incorrect or the basic submodule has not yet been configured not ready The figure below shows the assignment of the address space with submodules 1 and 2 Figure 4 3 Address space for configuration as 1 x 32 channel DI 32x24VDC BA MSI...

Page 17: ...bmodules 3 and 4 Figure 4 4 Address space for configuration as 1 x 32 channel DI 32x24VDC BA MSI with value status Reference You can find information on the module internal shared input shared output MSI MSO function in the section Module internal shared input shared output MSI MSO of the function manual PROFINET with STEP 7 V13 https support industry siemens com cs ww en view 49948856 ...

Page 18: ...rms 5 The module has no selectable diagnostics Diagnostics alarms for example cannot be output with STEP 7 TIA Portal 5 1 Status and error displays LED displays The figure below shows you the LED displays status and error displays of the DI 32x24VDC BA Figure 5 1 LED displays of the module DI 32x24VDC BA ...

Page 19: ...d error displays LED Meaning Remedy RUN ERROR Off Off Voltage missing or too low at backplane bus Switch on the CPU and or the system pow er supply modules Verify that the U connectors are inserted Check to see if too many modules are in serted Flashes Off Module is starting up On Off Module is ready Flashes Flashes Hardware defective Replace the module LED CHx Table 5 2 CHx status display LED CHx...

Page 20: ...V13 STEP 7 can be configured integrated as of version V5 5 SP3 PROFIBUS as of GSD version GSD revision V1 0 V5 1 PROFINET as of GSD version GSD revision V2 3 Operating mode DI Yes Counters No MSI Yes Supply voltage Rated value DC 24 V Valid range low limit DC 20 4 V Valid range high limit DC 28 8 V Power Power consumption from the backplane bus 1 05 W Power loss Power loss typ 3 W Digital inputs N...

Page 21: ...d max 1000 m unshielded max 600 m Encoders Connectable encoders 2 wire sensor Yes Permitted quiescent current 2 wire sensor max 1 5 mA Isochronous mode Isochronous mode application synchronized up to terminal No Interrupts diagnostics status information Diagnostics function No Interrupts Diagnostics interrupt No Hardware interrupt No Diagnostics alarms Monitoring of supply voltage No Wire break No...

Page 22: ...hannels and power supply of the electronics No Isolation Isolation tested with 707 V DC type test Ambient conditions Ambient temperature during operation Horizontal mounting position min 0 C Horizontal mounting position max 60 Vertical mounting position min 0 C Vertical mounting position max 40 C Distributed mode Prioritized startup Yes Dimensions Width 25 mm Height 147 mm Depth 129 mm Weights Wei...

Page 23: ... drawing A The dimensional drawing of the module on the mounting rail as well as a dimensional drawing with open front cover are provided in this appendix Always observe the specified dimensions for installation in cabinets control rooms etc Figure A 1 Dimensional drawing of the DI 32x24VDC BA module ...

Page 24: ...Index Digital input module DI 32x24VDC BA 6ES7521 1BL10 0AA0 24 Manual 12 2016 A5E32363711 AD Figure A 2 Dimensional drawing of the DI 32x24VDC BA module side view with open front cover ...

Reviews: