Technical specifications
CPU 1513R-1 PN (6ES7513-1RL00-0AB0)
34
Equipment Manual, 05/2021, A5E42009333-AC
Article number
6ES7513-1RL00-0AB0
Load memory
•
Plug-in (SIMATIC Memory Card), max.
32 Gbyte
Backup
•
maintenance-free
Yes
CPU processing times
for bit operations, typ.
80 ns
for word operations, typ.
96 ns
for fixed point arithmetic, typ.
128 ns
for floating point arithmetic, typ.
512 ns
CPU-blocks
Number of elements (total)
4 000; Blocks (OB, FB, FC, DB) and UDTs
DB
•
Number range
Number range: 1 to 59 999
•
Size, max.
1.5 Mbyte; For non-optimized block accesses, the
max. size of the DB is 64 KB
FB
•
Number range
0 ... 65 535
•
Size, max.
300 kbyte
FC
•
Number range
0 ... 65 535
•
Size, max.
300 kbyte
OB
•
Size, max.
300 kbyte
•
Number of free cycle OBs
100
•
Number of time alarm OBs
20
•
Number of delay alarm OBs
20
•
Number of cyclic interrupt OBs
20
•
Number of process alarm OBs
50
•
Number of startup OBs
100
•
Number of asynchronous error OBs
4
•
Number of synchronous error OBs
2
•
Number of diagnostic alarm OBs
1
Nesting depth
•
per priority class
24
Summary of Contents for 6ES7513-1RL00-0AB0