IM 155-6 PN ST interface module (6ES7155-6AU01-0BN0)
Equipment Manual, 10/2020, A5E03576904-AE
39
Compatibility
6
Compatibility between the versions of the IM 155-6 PN ST
The table below describes which version you can use in the configuration for which actually
plugged version of the IM 155-6 PN ST interface module. The table also describes the
functional differences of the versions of the IM 155-6 PN ST interface module.
IM 155-6 PN ST
configured
IM 155-6 PN ST plugged
Changes compared to previous version
V1.0.x
V1.1.x
V3.1.x
V3.3.x
V4.1.x
V1.0
✓
✓
✓
✓
✓
---
V1.1
---
✓
✓
✓
✓
•
The "Group diagnostics: Missing supply volt-
age L+" parameter can be set on the server
module
•
"Status of supply voltage L+ of the I/O mod-
ules" can be configured on the server module
V3.1
---
---
✓
✓
✓
•
User data 512 bytes
•
Station extension via ET-Connection
V3.3
---
---
---
✓
✓
•
Support of submodules
V4.1
---
---
---
---
✓
---
Note
IM 155-6 PN ST (6ES7155-6AU00-0BN0) with firmware version V4.1
You can upgrade the previous version of the IM 155-6 PN ST interface module (6ES7155-
6AU
00
-0BN0) to the firmware version V4.1. In this case configure the module as IM 155-6 PN
ST interface module (6ES7155-6AU
01
-0BN0) with firmware version V4.1.
Status of the supply voltage
Load voltage diagnostics are only valid if the station started up with a valid and complete
configuration.
•
For modules in the following table without a parameter assignment, the status of the
supply voltage is always signaled as "1" regardless of the actual status of the supply
voltage.
•
If a potential group is exclusively made up of modules without parameter assignment
from the table below, no group diagnostics "Missing supply voltage L+" is signaled for this