Page 32 of 49
Æ
Supply the PRB only with safety extra-Iow voltage to IEC 60634-4-41
"Generation as Functional Extra-Iow Voltage with Safe Electrical lsolation", DC
20, 4-28.8 V DC (+24 V typical).
Æ
The PRB must be operated with a grounded incoming supply. The reference
potential (ground) of the 24 V DC supply voltage must be connected to PE.
Æ
Be sure there is sufficient tensile load and observe the cable's minimum
bending
radii.
Pin No.
Name
Function
1
L1+
24 V DC
2
L2+
24 V DC
3 M1
Ground
4 M2
Ground
Fig. 23: Terminal assignment for the supply voltage interface
6.3.2.6
Connecting the signalling contacts
An electronic semi-conductor relay with potential-free contacts is provided for
signalling faults or the failure of the operating voltage. The signalling contact can be
connected to a controller's digital I/0 via the 15-pin terminal block on the front of the
PRB.
Æ
Be sure there is a sufficient tensile load and observe the cable's minimum
bending radii.
Pin - Nr.
Name
Function
6
11
Shared connector pin
7
12
Conducts potential from terminal 11 when SF LED is on (fault)
8
14
Conducts potential from terminal 11 when SF LED is out (ready)
Fig. 24: Terminal assignment for the signalling contact interface
When the PRB is deenergized, terminals 12 and 14 are separated from terminal
6.3.2.7
Connection scheme for wiring PRB
Fig. 25: Connection scheme PRB