SITOP PSU8200 3ph
Manual, 11.2014, C98130-A7638-A1-2-7629
25
Installation
5
WARNING
Hazard due to electric shock
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again. If this instruction is
not observed, touching live parts can result in death or serious injury.
5.1
Line-side connection
The SITOP PSU8200 3ph power supply is designed for connection to a 3-phase AC line
supply with a rated voltage of 400-500 V AC, 50/60 Hz.
Figure 5-1
Line supply connection
The line supply is connected using terminals L1, L2, L3 and PE (see Figure 5-1 Line supply
connection (Page 25)), and must be implemented according to IEC 60364 and EN 50178 .
A protective device (miniature circuit breaker or circuit breaker) and a disconnection unit for
the power supply must be provided. A ground-fault circuit interrupter is not permissible
against indirect contact as the only protective measure. This applies for the complete line
supply protected by the ground-fault circuit interrupter.