A.4
Diagnostics messages and maintenance events
[ID: 80188307851]
Diagnostics messages
A diagnostics message is generated for each diagnostics event and the DIAG LED on the RQ
4x120VDC-230VAC/5A CO HA flashes red or the MT LED lights up yellow.
The diagnostics messages can be read in the diagnostics buffer of the CPU, for example.
Diagnostic messages are assigned either channel-specific to an output or assigned as module
messages to all outputs. All channels are switched off for diagnostics messages that affect the
entire module. Only the corresponding relay contact is affected by diagnostics messages,
which refer to individual channels.
Table A-1
Diagnostics messages, their meanings and corrective measures
Diagnostics mes‐
sage
Error code Assignment
Meaning
Solution
Parameter as‐
signment error
10
H
Module
● Parameter assignment does not
match the terminal block used
● Incorrect parameter assignment
● Correct the parameter
assignment
● Check terminal block
1
Supply voltage
missing
11
H
Module
Missing or insufficient supply volt‐
age L+
Check the supply voltage L+
on the terminal block
Channel/compo‐
nent temporarily
unavailable
1F
H
Module
Firmware update is currently in pro‐
gress or has been canceled. The
module does not output any process
or substitute values in this state.
● Restart firmware update
● Wait for firmware update
Shutdown on but‐
ton activation
122
H
Module
The output disable switch was activa‐
ted
Pull and plug module
Retentive memo‐
ry in carrier mod‐
ule defective
154
H
Module
An error of the memory block on the
adapter module was detected during
startup
Replace carrier module
Retentive memo‐
ry in the terminal
block defective
155
H
Module
An error of the memory block on the
terminal block was detected during
startup
Replace terminal block
1
Only the terminal blocks (TB 45 ...) are suitable for operating I/O modules with IO redundancy.
Maintenance events
A maintenance event is generated for each maintenance required identified. The MT LED
lights up on the module.
Drivers, parameters, diagnostics messages and address space
A.4 Diagnostics messages and maintenance events
Digital Output Module RQ 4x120VDC-230VAC/5A CO HA (6DL1132-6HD50-0PK0)
34