Parameters
Value range
Default
Changing parame‐
ter settings in RUN
Efficiency range
Diagnostics: flutter error
(Page 23)
• Enabled
• Disabled
Disabled
Yes
Channel
Flutter monitoring: Mon‐
itoring window
(Page 23)
• 0.5 s
• 1 s to 100 s (can be set in 1 s-
increments)
0.5 s
Yes
Channel
Flutter monitoring: Num‐
ber of signal changes
(Page 23)
• Disabled
• 2 to 32
Disabled
Yes
Channel
• Disabled
• Rising edge
• Falling edge
• Falling and rising edge
Disabled
Yes
Channel
• Channel disabled
• NAMUR encoder
• Point of contact, unconnec‐
ted
• Point of contact, connected
with 10 kΩ
• NAMUR change-over con‐
tact
• Change-over contact, un‐
connected
• Change-over contact, con‐
nected with 10 kΩ
NAMUR encoder Yes
Channel
• None
• 0.5 s
• 1 s
• 2 s
None
Yes
Channel
1)
• Normal
• Inverted
Inverted
Yes
Channel
Potential group
(Page 26)
• Potential group of the left
module (dark gray terminal
block)
• New potential group (light
gray terminal block)
• No potential group (black
terminal block)
Use potential
group of the left
module
No
Module
1)
If you re-parameterize the "Digital input" parameter, an edge change is generated.
Parameters
6.2 Module/channel parameters
DI 16xNAMUR HA
20
Equipment Manual, 08/2019, A5E39293880-AD
Summary of Contents for 6DL1131-6TH00-0PH1
Page 6: ...Security information DI 16xNAMUR HA 6 Equipment Manual 08 2019 A5E39293880 AD ...
Page 8: ...Preface DI 16xNAMUR HA 8 Equipment Manual 08 2019 A5E39293880 AD ...
Page 10: ...2D Matrix code QR code EAN code DI 16xNAMUR HA 10 Equipment Manual 08 2019 A5E39293880 AD ...
Page 30: ...Parameters 6 5 Flutter monitoring DI 16xNAMUR HA 30 Equipment Manual 08 2019 A5E39293880 AD ...