Mounting and connecting
3.3 Connecting the HMI device
Basic Panels
Operating Instructions, 04/2012, A5E02421799-03
39
Procedure
.7
3
PP
t
ุPP
t
ุPP
t
352),%86
352),1(7
1.
Interconnect functional ground of the
HMI device with an grounding cable,
cross-section 4 mm
2
.
2.
Connect the grounding cable of the
HMI device to the equipotential
bonding rail.
3.3.3
Connecting the power supply
Stripping the cable
6 m
m
Use power supply cables with a
maximum cross-section of 1.5 mm
2
.
1.
Strip the ends of two power supply
cables to a length of 6 mm.
2.
Attach cable sleeves to the bare
cable ends.
3.
Fix the cable sleeve onto the cable
ends using the crimp pliers.