3355484128-03 

 

 

 

 

 

 

 

LED off, 

Device without power 

 

LED flashes alternately 2 Hz yellow/green 

Warning threshold exceeded 

 

LED static green 

MCB alright 

 

LED flashes alternately 2 Hz yellow/red 

Life cycle/max. switching cycles reached (no 

auto reset) 

 

LED flashes 0.75 Hz green 

Not configured with master device 

 

LED flashes 2 Hz red 

MCB tripped (Indication after power-on, 

acknowledge necessary) 

 

LED flashes 2 Hz green, min. for 3 s 

Internal process running e.g. pairing, internal 

test, firmware update, reset 

 

LED flashes 2 Hz yellow 

Selftest failed, Device/communication error 

 

LED flashes 5 Hz green 

Device Identification after ext. command 

 

 

Reset device keys to factory default (unpair from 

POC1000) 

Press button ≥ 10 s

 

After 3 s LED flashes 2 Hz green for 7 s. 

Then the LED flashes 10 Hz green for 2 s 

Acknowledge after trip 

1. Take care, that the cause of trip is removed 

2. Switch ON the device and press button < 3 s 

 

 