Siemens 599-06610 Technical Instructions Download Page 5

Flowrite™ 599 Series High Pressure Close-Off Two-Way Valves 2-1/2 to 6-inch  

Technical Instructions 

Flanged Iron Bodies ANSI Classes 125 and 250 

Document Number 155-758 

 

June 14, 2019 

Siemens Industry, Inc. 

Page 5

 

 

 

 

Table 4.  Cast Iron Valve Body Ratings. 

Temperature 

Pressure psig (kPa) 

°F 

°C 

ANSI Class 125 

ANSI Class 250 

–20 to 150 

–30 to 66 

200 (1387) 

500 (3447) 

200 

93 

190 (1310) 

460 (3171) 

250 

121 

175 (1206) 

415 (2861) 

300 

149 

165 (117) 

375 (2585) 

400 

204 

140 (965) 

290 (1999) 

450 

232 

125 (861) 

250 (1723) 

 

Table 5.  Maximum Water Capacity - U.S. Gallons per Minute. 

Valve 

Size 

Inches 

Pressure Differential - psi 

Cv\

10 

15 

20 

25 

30 

40 

50 

60 

75 

2-1/2 

63 

89  109  126  141  154  178  199  244  282  315  345  398  445  488 

546 

100  141  173  200  224  245  283  316  387  447  500  548  632  707  775 

866 

160  226  277  320  358  392  453  506  620  716  800  876  1012  1131  1239  1386 

250  354  433  500  559  612  707  791  968  1118  1250  1369  1581  1768  1936  2165 

400  566  693  800  894  980  1131  1265  1549  1789  2000  2191  2530  2828  3098  3464 

 

Table 6.  Maximum Water Capacity - Cubic Meters per Hour (m3/hr). 

Valve 

Size 

mm 

Pressure Differential - kPa 

10 

20 

30 

40 

50 

60 

80 

Kvs/ 

100 

150  200  300  400  500 

65 

5.4  17.1  24 

30 

34 

38 

42 

48 

54 

66 

76 

94 

108  121 

80 

8.5 

27 

38 

47 

54 

60 

66 

76 

85 

104  120  147  170  190 

100 

14 

43 

61 

75 

87 

97 

106  123  137  168  194  237  274  306 

125 

21 

68 

96  117  135  151  166  191  214  262  303  371  428  479 

150 

34  108  153  187  216  242  265  306  342  419  484  592  684  765 

 
 
 
 
 

Summary of Contents for 599-06610

Page 1: ...ge face to face dimensions meet ISA 75 03 standards Universal bonnet for direct coupled actuators Equal percentage flow characteristic Stainless steel trim ANSI Leakage Class IV EPDM O ring packing Application These Flowrite valves are recommended for chilled or hot water or 50 water glycol solutions ANSI 125 and ANSI 250 cast iron body rating Maximum recommended differential pressure for modulati...

Page 2: ...40 6 150 1 1 2 40 599 06614 Normally Closed 63 54 2 1 2 65 3 4 20 599 06615 100 85 3 80 3 4 20 599 06616 160 137 4 100 1 1 2 40 599 06617 250 214 5 125 1 1 2 40 599 06618 400 340 6 150 1 1 2 40 599 06619 Table 2 Product Numbers for ANSI 250 Valves Action Flow Rate Valve Line Size Stroke Valve Part Number Cv Kvs Inch mm Inch mm Normally Open 63 54 2 1 2 65 3 4 20 599 06620 100 85 3 80 3 4 20 599 06...

Page 3: ...solutions Medium temperature range 20 F to 250 F 7 C to 120 C Operating Maximum recommended differential pressure for modulating service 50 psi 345 kPa Rangeability 100 1 Close off pressures See Tables 7 and 8 Close off ratings According to ANSI FCI 70 2 Leakage rate Class IV 0 01 of Cv Flow characteristic Equal Percentage Miscellaneous Canadian Registration Numbers 0H7645 5 0C0838 9 Mounting loca...

Page 4: ...Stroke Kit No ANSI 125 Normally Open 599 06610 2 1 2 65 63 3 4 20 599 09250 599 06611 3 80 100 3 4 20 599 09251 599 06612 4 100 160 1 1 2 40 599 09252 599 06613 5 125 250 1 1 2 40 599 09253 599 06614 6 150 400 1 1 2 40 599 09254 Normally Closed 599 06615 2 1 2 65 63 3 4 20 599 09255 599 06616 3 80 100 3 4 20 599 09256 599 06617 4 100 160 1 1 2 40 599 09257 599 06618 5 125 250 1 1 2 40 599 09258 59...

Page 5: ...20 25 30 40 50 60 75 2 1 2 63 89 109 126 141 154 178 199 244 282 315 345 398 445 488 546 3 100 141 173 200 224 245 283 316 387 447 500 548 632 707 775 866 4 160 226 277 320 358 392 453 506 620 716 800 876 1012 1131 1239 1386 5 250 354 433 500 559 612 707 791 968 1118 1250 1369 1581 1768 1936 2165 6 400 566 693 800 894 980 1131 1265 1549 1789 2000 2191 2530 2828 3098 3464 Table 6 Maximum Water Capa...

Page 6: ...es 2 1 2 to 6 inch Document Number 155 758 Flanged Iron Body ANSI Classes 125 and 250 June 14 2019 Page 6 Siemens Industry Inc Figure 2 Water Capacity Graph Selection Example Select a valve given Required flow 500 gpm Desired pressure drop 5 psi Select a 5 inch 125 mm valve Cv 250 ...

Page 7: ...c SKD SKC Normally Open 2 1 2 65 200 1378 3 80 200 1378 4 100 200 1378 5 125 200 1378 6 150 200 1378 Normally Closed 2 1 2 65 200 1378 3 80 200 1378 4 100 200 1378 5 125 200 1378 6 150 200 1378 Action Valve Size Inch mm Spring Return 8 Inch 12 Inch 3 to 8 psi 21 to 55 kPa 10 to 15 psi 69 to 103 kPa 3 to 8 psi 21 to 55 kPa 10 to 15 psi 69 to 103 kPa 15 psi 103 kPa 0 psi 0 kPa Normally Open 2 1 2 65...

Page 8: ...ous actuators for additional information Normally Open Normally Closed Figure 3 Operation Sizing The sizing of a valve is important for correct system operation An undersized valve will not have sufficient capacity at maximum load An oversized valve may initiate cycling and the seat and throttling plug may be damaged because of the restricted opening Correct sizing of the control valve for actual ...

Page 9: ...any position between Horizontal to the valve and Vertical above the valve It is not recommended to install the valve assembly below horizontal or upside down Figure 4 Recommended Installation Orientations For flange dimensions and bolt hole information see 155 303P25 TB 248 Allow sufficient space for servicing the valve and actuator See Table 11 for valve body dimensions See Figure 7 and Table 10 ...

Page 10: ...al 1 Packing Cartridge Assembly 1 2 Gasket 1 Copper 3 Packing Spring 1 Stainless Steel 4 Packing Bearing 1 Bronze 5 Cap Screw 4 8 Plated Steel 6 Bonnet 1 Cast Iron 7 Gasket 1 8 Valve Body 1 Cast Iron 9 Stem and Plug Assembly 1 Stainless Steel 10 O ring 1 EPDM 11 Cap 1 Cast Iron 12 Cap Screw 4 Plated Steel Packing Kit 599 08020 Items 1 2 3 4 13 Sleeve 1 Cast Iron 14 Sleeve Seal 1 Rebuild Repack Kit...

Page 11: ...valve dimensions Figure 7 Dimensions Table 10 Dimensions of the Actuator and Recommended Service Envelope Dimensions in Inches Millimeters Actuator Prefix Code Actual Height of Actuator H1 Service Height H Actuator Width or Diameter of W1 Service Width W 8 Pneumatic 283 14 1 8 359 26 660 8 3 4 222 diameter 21 450 12 Pneumatic 287 17 7 8 454 30 762 15 1 8 384 diameter 27 686 SKD 274 11 13 16 300 19...

Page 12: ...A Page 12 Table 11 Valve Dimensions and Weight Action Valve Size inch mm ANSI Class 125 ANSI Class 250 Dimensions Inches mm Weight lbs kg Dimensions Inches mm Weight lbs kg A B C A B C Normally Open 2 1 2 65 11 276 11 281 4 7 8 123 62 28 11 1 2 292 11 281 5 123 78 35 3 80 11 3 4 299 12 1 4 312 5 5 16 135 79 35 12 1 2 318 12 1 4 312 5 5 16 135 102 46 4 100 14 352 13 9 16 345 6 5 16 160 129 58 14 1 ...

Reviews: