Connecting
5.1 Connecting measuring sensors
2 AI I 2/4WIRE HF analog electronic module (6ES7134-4MB02-0AB0)
24
Manual, 04/2007, A5E01076111-01
Non-isolated measuring encoders
The non-isolated measuring encoders are connected to the local ground potential.
Depending on local conditions or interference, potential differences U
CM
(static or dynamic)
can occur between the locally distributed measuring points.
If the permitted value for U
CM
is exceeded, there must be equipotential bonding conductors
between the measuring points.
The following schematic representation illustrates the connection of non-isolated measuring
encoders to an optically isolated analog input module.
5
4
1
2
3
0
0
/
0
0
0
8
&0
$'8
8
,62
P$
P$
①
Logic
②
Backplane bus
③
Ground bus
④
Equipotential bonding conductor
⑤
Non-isolated measuring encoders
Operating four-wire transmitters on an external voltage supply
If there is electrical isolation between the output and the transmitter supply, you can connect
the transmitter to the 2 AI I 2/4WIRE without the need for additional connections.