Differential Pressure Monitor Owner’s Manual
+
-
1 2 3
+
-
24V TRUNK
PIN #1
PIN #1
PRESSURE SIGNAL
TO DPM
SEN0177R1
Figure 3. RPT Circuit Board.
Operating and Power Specifications
Operating temperature
65
°
to 85
°
F (18.3
°
to 29.5
°
C)
Operating range
24 Vac, 50/60 Hz
Power consumption
1.4 VA, Class 2, at 24 Vac
Pressure Signal Output Definition and Specification
The
pressure signal output
is a digital pulse signal that represents the measured pressure
difference across the sensor.
Operating Range
0-5 volt rectangular wave, 0-10 KHz
Recommended Wire
2 Conductor, 18 AWG Shielded Cable.
Recommended max.
wire length
500 ft (152.4 m)
6