Siemens 1000 series Installation Instructions Download Page 3

Document No. 540-743 

Installation Instructions  

September 10, 2009 

Mounting Information 

Locate the sensor: 

 

according to design specifications and local 
regulations. 

 

where the air circulates around it freely (not 
in recessed areas or behind doors). 

 

allowing a minimum of 4 inches (100 mm) 
free space above and below for proper 
airflow, the front cover removal tool, and the 
computer communication cable. 

 

away from drafts caused by doors, windows, 
outside walls, air registers, pipes, return air 
plenums, etc. 

 

away from heat sources such as strong 
lights, fireplaces, direct sunlight, etc. 

 

on an inside wall (preferably), about 5 feet 
(1.5 m) above the finished floor. 

NOTE: 

While not recommended, if you must mount 
the sensor on exterior brick or cement-type 
walls, see 

Accessories

Drywall Mounting (No Rough-in), 
Typical 

1.  Mark the center (cable) hole and the mounting 

hole locations using the sensor base plate as a 
template. See Figure 2.  

 

CAUTION: 

 

For drywall mounting, only use the top 
and bottom holes. 

2.  Drill two 3/16-inch (4.8 mm) mounting holes. 

3.  Cut a 1-inch (25 mm) center hole with a hole 

saw. 

4.  If using screws to attach the sensor, insert two 

plastic wall anchors. 

5.  Pull about three inches (75 mm) of the cable 

through the mounting hardware in the order 
shown. See Figure 2. 

 

Figure 2.  Drywall Mounting (No Rough-in), Typical. 

6.  Mount the sensor base plate on the wall, noting 

the UP arrow on the stabilizer plate: 

a.  Install either the two mounting screws 

provided, the drive rivets provided, or 
spring clips, but do not tighten. 

CAUTION: 

 

Pounding too hard or over-tightening may 
cause the sensor base plate to crack or 
bend. 

b.  Level the sensor base plate for 

appearance. 

c.  Tighten the two mounting screws to the 

sensor base plate. 

7.  Cut the cable, leaving about 3 inches (75 mm) 

on the sensor side of the drywall. 

CAUTION: 

 

For retrofits: Before cutting the cable, 
make sure it is disconnected from the 
UC/MBC/RBC. 

8.  Unplug the terminal block from the back of the 

printed circuit board (PCB) and terminate the 
cable wires at the sensor terminal block. For six-
position terminal blocks, see Figure 3. For four-
position terminal blocks, see Figure 4. Also see 
Figure 5 (MBC/RBC) or Figure 6 (UC). Reinstall 
the terminal block. 

Siemens Building Technologies, Inc. 

Page 3 of 5

 

Summary of Contents for 1000 series

Page 1: ...le where applicable and sensor color C C F F A desert beige B white e g 544 770FA for F desert beige Warning Caution Notations WARNING Personal injury loss of life may occur if a procedure is not performed as specified CAUTION Equipment damage or loss of data may occur if you do not follow procedure as specified Item Number 540 743 2 Rev DA Figure 1 Room Temperature Sensor Showing All Optional Fea...

Page 2: ... 9 cm 155 252P25 TB 238 536 666 Mounting Strap standard light switch plate field supplied to mount sensor on 2 4 electrical box 540 040 540 237 544 782 Single Adapter Base Mounting Kit 2 4 boxes all single sensor installations on walls with oversized holes paint lines etc that need to be covered and on exterior brick cement type walls Kit includes Electrical Box Adapter Plate Assembly 192 495 Adap...

Page 3: ...nting holes 3 Cut a 1 inch 25 mm center hole with a hole saw 4 If using screws to attach the sensor insert two plastic wall anchors 5 Pull about three inches 75 mm of the cable through the mounting hardware in the order shown See Figure 2 Figure 2 Drywall Mounting No Rough in Typical 6 Mount the sensor base plate on the wall noting the UP arrow on the stabilizer plate a Install either the two moun...

Page 4: ...1 Tighten the sensor front retaining screw See Figure 2 12 Terminate the other end of the wires either a at the MBC RBC module terminal block s Figure 5 or b at the appropriate UC terminal blocks Figure 6 The installation is now complete Terminating the Cable Wires NOTE 1 All connections for one sensor must be terminated in the same cabinet whether MBC RBC MEC or UC 2 Unitary Controller installati...

Page 5: ... the locator by removing the two screws and lightly rocking the locator to pull it free b Tighten the two mounting screws to the sensor base plate 2 Untie the twist tie and pull about three inches 75 mm of the sensor cable into the space CAUTION Over tightening may cause the sensor base plate to crack or bend 3 If you have a single sensor electrical box install the electrical box adapter plate See...

Reviews: