Electrical installation
5.5
Connection diagrams
•
Take note of the related operating instructions of the integrated devices!
•
You can find more connection diagrams at www.sick.com.
5.5.1
V200/V300 on UE410 Flexi with external device monitoring (EDM) and with
restart interlock both for V200/V300 as well as for emergency switching off
The V200/V300 safety camera system can be integrated into a relay controller/contactor
controller with the aid of the modular UE410 Flexi (UE410-MU with expansion UE410-XU)
safety controller. Operation is with external device monitoring and internal restart interlock
on the V200/V300 as well as restart interlock for emergency switching off.
Principle of operation
When the light path on the V200/V300 is clear and the input conditions on the UE410 are
valid, the system is ready for switch on and waits for an input signal/switch on signal. The
system’s corresponding logic path is enabled by pressing and releasing the related button
S1. The related output on the UE410 carries power. If the input conditions are no longer
met, then the related outputs on the UE410 shut down.
Possible errors
Cross-circuits and short-circuits on the connecting cables for the V200/V300 are detected
and result in “lock-out” (see page 50). Malfunctions on the contactors K1 to K4 are
detected. The shutdown function is retained. (If the button S1.x is tampered with (e.g. by
jamming) the system will not re-enable the output circuits.
Notes
Fig. 24: Connection diagram
V200/V300 at UE410 Flexi
FE
+24 V
0 V
1
2
3
4
5
6
7
8
Internal
teach-in
key
RESTART
+24 V
TEACH/SYNC
EDM
OSSD1
OSSD2
GND
FE
K3
K1
k1
k2
S1.1
I1 I2 A1 X1 X2 S1 S2 S3
I3 I4 A2 Q1 Q2 Q3 Q4 EN
K4
K2
Κ
UE410-MU/XU
k3
k4
S1.2