7.2.3
Teaching in the switching window, IO-Link: Window (window mode)
When the object is located within the taught-in switching window, the digital output is
active.
NOTE
UC12-xxxx1, UC12-xxxx5: The hysteresis points apply outwards from the configured
switching window points.
UC12-xxxxE: The hysteresis points apply inwards from the configured switching window
points.
Teach in the switching window
2
1
1.
Position the object at
1
.
2.
Press the teach-in button for 5 seconds until the green LED flashes.
✓
LED flashes orange and green alternately.
3.
Position the object at
2
.
✓
LED flashes orange and green alternately.
4.
Press the teach-in button for 1 second.
✓
The switching points are taught-in. The device automatically switches to normal
operation mode.
7.2.4
Teaching in the background, IO-Link: Window
±
8% (ObSB)
When the object is located either below the taught-in reflector -10 mm (IO-Link: -8 %) or
above the taught-in ref10 mm (IO-Link: +8 %), the digital output is active.
Teach in the background
1
– 8 %
+ 8 %
Figure 9: UC12-xxxxE
OPERATION
7
8010984/1BNB/2022-05-12 | SICK
O P E R A T I N G I N S T R U C T I O N S | UC12
21