COMMISSIONING
Volume V
Time t
Time t
Pulse output
Fig. 27: Example behavior of the pulse output (the larger the slope of the volume, the more
pulses are output)
7.3.11
Configuring the Q2 digital input
There are two selectable logic variants for the Q2 input in the
Q2 Mode
menu:
−
Input AND with Q1
−
Input OR with Q1
This function can be used, for example, to create a control logic using the signals from
two T-Easic
®
devices and using only one digital PLC input. In this case, the Q1 output of
the T-Easic
®
B serves as the Q2 digital input of the T-Easic
®
A, and the Q1 output of the
T-Easic
®
A is connected to the PLC.