CAUTION
Restricted field evaluation in the dual protective field mode
In the
Dual protective fields
field mode, protective field 2 is not evaluated in the areas in
which a contour is configured as reference.
b
Monitor the contour outside the area of protective field 2.
You define the contour as a reference in the CDS field set editor.
Vertical operation
In vertical operation (for access protection and hazardous point protection), the protec‐
tive fields must, in accordance with IEC 61496-3, be configured using the contour as
reference function. In addition, the total response time of the device is not allowed to
exceed 90 ms.
Figure 65: Contour as reference for vertical operation
1
2
Contours of the machine opening
3
Contour segment
NOTE
Lateral, vertical boundaries of the opening (e.g., door frame) together with the floor are
particularly suitable as a reference. If the position of the safety laser scanner is
changed in one or more planes, the distance to the reference changes. The device then
switches its safety outputs to the OFF state or signals
Protective field interrupted
.
7.11
Monitoring cases
Overview
The device supports a configuration with multiple monitoring cases. By switching the
monitoring case you can switch to different monitoring conditions in the case of a
change to the monitoring situation.
CONFIGURATION
7
8013291/ZA19/2019-11-14 | SICK
O P E R A T I N G I N S T R U C T I O N S | S3000 PROFINET IO, S3000 PROFINET IO-OF
83
Subject to change without notice