Addendum Operating Instructions
Chapter
8
S3000 PROFINET IO/IO OF
8013291/YY95/2016-02-05
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
31
Subject to change without notice
Technical specifications
8.2
Process image S3000 PROFINET IO/IO OF Professional
The process contains data on eight monitoring cases and eight field sets.
8.2.1
INPUT
Bit
Description
0.0
Protective field unoccupied
0.1
Warning field unoccupied
0.2
Simultaneous protective field unoccupied
0.3
Simultaneous warning field unoccupied
0.4
Reset required (protective field)
0.5 Reserved
0.6
Reset required (simultaneous protective field)
B
yt
e
0
0.7 Reserved
1.0 Contamination
1.1
Monitoring case valid
1.2
Monitoring case number – Bit 0
1.3
Monitoring case number – Bit 1
1.4
Monitoring case number – Bit 2
1.5
Monitoring case number – Bit 3
1.6 Reserved
B
yt
e
1
1.7 Reserved
2.0 Reserved
2.1 Reserved
2.2 Reserved
2.3 Reserved
2.4 Reserved
2.5 Reserved
2.6 Reserved
B
yt
e
2
2.7 Reserved
3.0 Reserved
3.1 Reserved
3.2 Reserved
3.3 Reserved
3.4 Reserved
3.5 Reserved
3.6 Reserved
B
yt
e
3
3.7 Reserved
Tab. 9: Process image
S3000 PROFINET IO/IO
OF
Professional INPUT