Addendum Operating Instructions
Chapter
6
S3000 PROFINET IO/IO OF
8013291/YY95/2016-02-05
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
19
Subject to change without notice
Configuration
Parameter
Meaning
Setting
F_SIL
Safety integrity level (NoSIL, SIL1 or SIL2) of
the S3000 PROFINET IO/IO
8
OF
Depending on
application
F_CRC_Length
Anticipated length of the CRC checksum in
the PROFIsafe telegram
3 Byte CRC
F_Block_ID
The value 1 in the parameter indicates that
the data set for the value of F_iPar_CRC is
extended by 4 bytes. You are not allowed to
change the parameter.
0
F_Par_Version
Implemented PROFIsafe version. You cannot
change this parameter.
1
F_Source_Add
PROFIsafe source address. Must be unique in
combination with the PROFIsafe destination
address and is assigned automatically.
1 to 65 534
F_Dest_Add
PROFIsafe destination address. Must be
unique in combination with the PROFIsafe
source address and is assigned
automatically.
Notes:
The PROFIsafe address for the
S3000 PROFINET IO/IO
8
OF must match
this value (see section 6.2.1 on page 20).
You must enter the default value for the
parameter
F_Dest_Add
using CDS (see
1 to 65 534
F_WD_Time
Monitoring time (“Watchdog time”) for the
cyclic service. If no valid PROFIsafe telegram
is exchanged between the
S3000 PROFINET IO/IO
8
OF and the FPLC
within the set monitoring time, both will
proceed to the safe status, i.e. they assign
themselves failsafe values.
The monitoring time should be sufficiently
long to tolerate minor delays in communica-
tion. In the event of an error however, it must
not unnecessarily delay the system response
of the S3000 PROFINET IO/IO
8
OF or that of
the FPLC.
Depending on the
application from
1 to 65 535 ms
2)
Cannot
be
changed.
Tab. 5: PROFIsafe
parameters for the
S3000 PROFINET IO/IO
OF