background image

12

Annex

12.1

Compliance with EU directives

EU declaration of conformity (extract)

The undersigned, representing the manufacturer, herewith declares that the product is
in conformity with the provisions of the following EU directive(s) (including all applicable
amendments), and that the standards and/or technical specifications stated in the EU
declaration of conformity have been used as a basis for this.

Complete EU declaration of conformity for download

You can call up the EU declaration of conformity and the current operating instructions
for the protective device by entering the part number in the search field at

www.sick.com

 (part number: see the type label entry in the “Ident. no.” field).

12 

ANNEX

32

O P E R A T I N G   I N S T R U C T I O N S | ReLy EMSS3

8023937/2019-10-11 | SICK

Subject to change without notice

Summary of Contents for ReLy EMSS3

Page 1: ...O P E R A T I N G I N S T R U C T I O N S ReLy EMSS3 Safety relay...

Page 2: ...sible within the limits of the legal determination of Copyright Law Any modifica tion abridgment or translation of this document is prohibited without the express writ ten permission of SICK AG The tr...

Page 3: ...xternal device monitoring 10 3 2 6 Cross circuit detection 10 3 2 7 Status indicators 10 4 Project planning 12 4 1 Manufacturer of the machine 12 4 2 Operating entity of the machine 12 4 3 Design 12 4...

Page 4: ...al data 25 10 1 Data sheet 25 10 2 Dimensional drawings 29 10 3 Internal circuitry 30 11 Ordering information 31 11 1 Ordering information for ReLy 31 12 Annex 32 12 1 Compliance with EU directives 32...

Page 5: ...manufacturer and the entity operating the machine in which the device is to be integrated Area of responsibility Target group Specific chapters of these operating instruc tions 1 Manufacturer Project...

Page 6: ...er which may lead to moderate or minor injuries if not prevented NOTICE Indicates a situation presenting possible danger which may lead to property damage if not prevented NOTE Indicates useful tips a...

Page 7: ...tentionally generated and or used conductor bound RF energy that is required for the inner function of the device itself occurs The safety relay must only be used within the limits of the prescribed a...

Page 8: ...sk a person is considered qualified when he she has the expertise and expe rience in the relevant field and is sufficiently familiar with the application of the protec tive device on the machine to be...

Page 9: ...her Actuators with positively guided contacts are connected to the enabling current paths 3 2 Product characteristics 3 2 1 Device overview RELY PWR OUT 13 23 I1 Y1 14 24 I2 Y2 A2 S1 33 A1 R1 34 1 2 3...

Page 10: ...detected on the safety capable inputs 3 2 7 Status indicators LEDs RELY PWR OUT 13 23 I1 Y1 14 24 I2 Y2 A2 S1 33 A1 R1 34 X1 X2 PWR OUT 13 23 I1 Y1 14 24 I2 Y2 A2 R1 A1 S1 X1 X2 EMSS3 1099973 RELY 33...

Page 11: ...reen Application diagnostic output reset required Further topics Status indicator LED page 23 PRODUCT DESCRIPTION 3 8023937 2019 10 11 SICK O P E R A T I N G I N S T R U C T I O N S ReLy EMSS3 11 Subj...

Page 12: ...risk assessment may require the entity operating the machine to meet the obligations of a manufac turer b Apart from the procedures described in this document the components of the safety relay must...

Page 13: ...nected via safety sen sors or safety switches in order to switch the enabling current paths 4 4 1 Enabling current paths DANGER Hazard due to lack of effectiveness of the protective device b Ensure th...

Page 14: ...rlock A reset pushbutton must be connected to allow the restart interlock to be used The reset pushbutton must be attached outside of the hazardous area It must not be possi ble to access the reset pu...

Page 15: ...turer and user must define the type and frequency of the thorough checks on the machine on the basis of the application conditions and the risk assessment Determination of the thorough checks must be...

Page 16: ...is done in accordance with EN 50274 and electrical installation in accordance with IEC 60204 1 in the control cabinet with enclosure rating IP54 Mounting must be done on a non flammable base Mounting...

Page 17: ...mounting rail 5 4 Module exchange Approach 1 Disconnect module and the connected components from all voltage sources 2 Take front connector with connected cables off the defective device Press the un...

Page 18: ...the new module First mount in the module with bent hook and then engage in the housing Click Figure 8 Mount the front connector The front connector engages with an audible click 5 MOUNTING 18 O P E R...

Page 19: ...Electrical installation is done in conformity with IEC 60204 1 The mounting rail is connected to the functional earth The voltage supply and connected signals meet the requirements for safety extra lo...

Page 20: ...enabling current path and external device monitoring EDM must be wired within the control cabinet 3 Connect dual channel switching elements of the safety sensors between X1 and I1 or X2 and I2 4 Use w...

Page 21: ...connected loads with varistors or RC elements The response times will increase depending on the sup pressor used Further topics Connection diagrams page 15 ELECTRICAL INSTALLATION 6 8023937 2019 10 1...

Page 22: ...mounting or the electrical installation After exceptional events such as after manipulation has been detected after modification of the machine or after replacing components The thorough check ensure...

Page 23: ...y voltage All LEDs All colors Initialization with LED test PWR O Green No fault PWR Red Supply voltage too low temporarily or per manently Internal error PWR Red green Error Additional LEDs flash for...

Page 24: ...in accordance with national waste disposal regulations Complementary information SICK will be glad to help you dispose of these devices on request 9 DECOMMISSIONING 24 O P E R A T I N G I N S T R U C...

Page 25: ...erous failure on demand 2 For operating heights 2 000 m above sea level 5 10 5 5 10 4 5 10 3 For operating heights 2 000 4 000 m above sea level 2 5 10 4 2 5 10 3 5 10 3 TM mission time 20 years ISO 1...

Page 26: ...l data inputs I1 I2 S1 Input voltage HIGH 24 V DC 11 V DC 30 V DC Input voltage LOW 0 V DC 3 V DC 5 V DC Input capacity 15 nF Input current 4 mA 6 mA Reset time Manual 250 ms Automatic 250 ms Actuatio...

Page 27: ...A IEC 60947 5 1 DC switching capacity 0 1 W 200 W see figure 10 page 28 AC switching capacity 0 1 VA 1 500 VA Switching frequency 1 Hz Mechanical service life 10 106 switching operations Contact fuse...

Page 28: ...condensing for climatic con ditions according to IEC 61131 2 Emitted interference In accordance with IEC 61000 6 4 Immunity to interference In accordance with IEC 61326 3 1 In accordance with IEC 610...

Page 29: ...al service life 1 Switching operations 1 000 2 Switching current A 10 2 Dimensional drawings 20 1 18 85 5 87 7 124 6 64 4 128 3 78 7 120 7 Figure 12 Dimensional drawing TECHNICAL DATA 10 8023937 2019...

Page 30: ...10 3 Internal circuitry Figure 13 Internal circuitry 10 TECHNICAL DATA 30 O P E R A T I N G I N S T R U C T I O N S ReLy EMSS3 8023937 2019 10 11 SICK Subject to change without notice...

Page 31: ...r ReLy Table 13 Ordering information Part Usage Type code Part number ReLy EMSS3 Safety switches RLY3 EMSS3 1099973 ORDERING INFORMATION 11 8023937 2019 10 11 SICK O P E R A T I N G I N S T R U C T I...

Page 32: ...l specifications stated in the EU declaration of conformity have been used as a basis for this Complete EU declaration of conformity for download You can call up the EU declaration of conformity and t...

Page 33: ...smantle front connector 17 8 Mount the front connector 18 9 Terminals on front connector 20 10 Switch off delay without continuous arcing 28 11 Electrical service life 29 12 Dimensional drawing 29 13...

Page 34: ...cal data 25 7 Electrical data operating data 26 8 Electrical data inputs I1 I2 S1 26 9 Electrical data test pulse outputs X1 X2 R1 26 10 Electrical data application diagnostic output Y1 Y2 26 11 Elect...

Page 35: ...LIST OF TABLES 14 8023937 2019 10 11 SICK O P E R A T I N G I N S T R U C T I O N S ReLy EMSS3 35 Subject to change without notice...

Page 36: ...8080 7425 E Mail enquiry my sick com Mexico Phone 52 472 748 9451 E Mail mexico sick com Netherlands Phone 31 0 30 229 25 44 E Mail info sick nl New Zealand Phone 64 9 415 0459 0800 222 278 tollfree...

Reviews: