O P E R AT I N G I N S T R U C T I O N S | L F P I N OX
8019921/15H0 / 2019-09-30 | S I C K A G
Irrtümer und Änderungen vorbehalten
2 2
7
COMMISSIONING
Commissioning
1. Mount the sensor as appropriate to the installation conditions, see
2. Log in to expert mode, see
3. Select measuring mode.
•
Access the EXPRT-CONFIG-MeasMd menu using the arrow and Set pushbut-
tons.
•
HiSpd: max. length = 2,005 mm, response time < 400 ms
•
HiAcc: max. length = 6,005 mm, response time < 2,800 ms, more stable mea
-
sured values, recommended for liquids with low DK values and where TrsHld
is < 70.
4. Teach in static sources of interference in the tank.
•
Static sources of interference in the tank generated by pipes, struts, cou-
plings, or cleaning balls are taught into the system as standard.
•
Access the EXPRT-CONFIG-CalRng menu using the arrow and Set pushbuttons.
Where the following applies:
•
Teach-in depth starts from the LFP process connection
•
The teach-in depth should cover all interference signals
•
Maximum teach-in depth (recommended) = probe length
•
Set the value range: 95 mm … 6,005 mm
•
If the tank cannot be emptied completely, the CalRng teach-in depth must be
adapted accordingly.
•
The level must be at least 200 mm under the CalLen and/or below the end of
the probe.
5. Run the AutCal function.
•
Access the AutCal menu using the arrow and Set pushbuttons.
•
The following applies: The probe must not be covered with liquid in the CalRng
set in step 4 (teach-in depth + 200 mm).
•
Use the Set pushbutton to confirm the AutCal menu item and then use it again
to confirm the Ok? prompt.
•
The AutCal function is confirmed with !CalOK.
6. Analyze the signal quality.
•
The signal quality can be analyzed when the device is installed,
see
“8.4.9 Evaluating signal quality”
•
In the event of problems:
•
Reduce the value in the EXPRT-CONFIG-TrsHld menu.
•
Set parameter to HiAcc in the EXPRT-CONFIG-MeasMd menu.
•
Switch on filters in the Set filters menu.
•
Reduce the parameter in the EXPRT-CONFIG-MaxCol menu.
7.
Configure the filter (see
“8.4.2 Filtering measured values”
8. Run maximum change of level / plausibility check
(see
“8.4.2 Filtering measured values”
).
9.
Configure the outputs (see