NOTE
When the estimator is turned on and MAXACC and MAXDEV are not configured,
dev_thr_err signal and DTE flag are set to "1".
7.3.2
Free running mode
In free running mode, the SYNC signal is automatically created by the DSL Master, for
which the maximum frame transmission frequency is used (see
). The free
running mode is the standard DSL Master operating mode at start-up.
This operating mode can also be selected manually, by setting the
ES
value in the
SYNC_CTRL
register to "0".
NOTE
It should be noted that in free running mode, no account is taken of the signals at the
SYNC input.
The polling of the position and rotation speed values is explained in
.
Figure 19: Polling of position registers in free running mode
Figure 20: Polling of rotation speed registers in free running mode
7.3.3
SYNC mode
In SYNC mode, the DSL Master depends on a prepared cyclic control signal. This control
signal triggers position measurements and enables polling of position and rotation
speed values synchronously with the control signal. The control signal must be applied
to the SYNC input and have the characteristics prescribed for the DSL Master (see
).
The position is available after a set delay in relation to the leading edge of the control
signal.
When SYNC mode is used the following points must be noted:
7
CENTRAL FUNCTIONS
64
T E C H N I C A L I N F O R M A T I O N | HIPERFACE DSL
®
8017595/ZTW6/2018-01-15 | SICK
Subject to change without notice