HC8X Heat Control
Electrical Installation
8010043
©
SICK AG · All rights reserved
3-21
3
Electrical Installation
3.1
Overview of Installation Steps
Connect the power electronics supply voltage
Connect the heating circuits
Connect the temperature sensors (PT100)
Connect the optical fibers
Connect the control electronics supply voltage via the mains socket
Short-circuit caused by frayed ends
Provide all stranded individual wires with suitable connector sleeves before their con-
nection to the respective terminal / terminal block.
Fig. 3-1:
Terminal-Side Overall View of the HC8X
1
2
3
4
5
X10
X1
X9
X2
X3
X4
X5
X6
X7
X8
1
Socket for mains connection with fuse holder and system voltage switch-over 115 V/230 V,
50
–
60 Hz
2
Optical fiber connection
3
X10 plug-type terminal strip for PT100 temperature sensors
4
X9 plug-type terminal strip for power electronics supply voltage
5
X1 – X8 plug-type terminal strip for heating circuits
3.2
Connecting the Power Electronics Supply Voltage
Destruction of electrical components by overvoltage!
Connect only a Y-connected supply line (3 P + N + PE).
The supply voltage may be 230 V, 50
–
60 Hz maximum.
1.
Unscrew two screws from the case cover.
2.
Remove the case cover and pull off the ground conductor.
3.
Select the wire cross-sections according to the current load and the circuit fuse.
4.
Carefully connect the wires of the supply line to the terminals L1, L2, L3, N and PE of
the plug-type terminal strip X9. Firmly tighten the clamping screws.