Chapter
11
Operating instructions
Flexi Classic
96
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
8011509/YPP0/2015-10-26
Subject to change without notice
Technical specifications
11
Technical specifications
11.1 Data sheet
11.1.1
UE410-MU/UE410-XU modules
Minimum
Typical
Maximum
Supply circuit (A1, A2)
Supply voltage U
B
19.2 V DC
24 V DC
30 V DC
Type of supply voltage
PELV or SELV
The current of the power supply unit for the main
module has to be limited to a maximum of 6 A —
either by the power supply unit itself or by a fuse.
Residual ripple U
ss
–
–
3 V
Power consumption
–
–
3 W
Maximum switch-on time
–
–
60 s
Short-circuit protection
4 A gG with tripping characteristic B or C
Input circuit (I1-I4, EN, S1-S3)
Number of inputs
–
–
8
Input voltage (high)
13 V DC
–
30 V DC
Input voltage (low)
–5 V DC
–
5 V DC
Input current (high)
2.4 mA
3 mA
3.8 mA
Input current (low)
–2.5 mA
–
2.1 mA
Input capacitance
9 nF
10 nF
11 nF
Minimum switch-off time
(I1/I2)
program 3.1, 7, 8
7 ms
–
–
Minimum switch-off time
10)
(I1/I2)
program 1, 2, 4, 5, 6, 9
20 ms
–
–
Minimum switch-off time
10)
(I1/I2)
pressure sensitive mat
20 ms
–
–
Minimum switch-off time
10)
(I3/I4)
program 1, 2, 7, 8, 9
7 ms
–
–
Minimum switch-off time
10)
(I3/I4)
program 4, 5, 6
20 ms
–
–
Minimum switch-off time
10)
(X1-I1/X2-I2) program 3.2
70 ms/20 ms –
–
Minimum switch-off time (EN)
7 ms
–
–
Maximum break time of the input
signal without switching of the
outputs (Q1-Q4)
–
–
1 ms
10)
Time without sensor, the data for the sensors connected apply in addition.
Tab. 39: Data sheet
UE410-MU/UE410-XU