![SICK Flexi Classic series Operating Instructions Manual Download Page 107](http://html.mh-extra.com/html/sick/flexi-classic-series/flexi-classic-series_operating-instructions-manual_1264302107.webp)
Operating instructions
Chapter
11
Flexi Classic
8011509/YPP0/2015-10-26
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
107
Subject to change without notice
Technical specifications
Minimum
Typical
Maximum
Safety specific characteristics
All these data are based on an ambient temperature of +40 °C.
Safety integrity level
SIL3 (IEC 61
508)
SIL claim limit
31)
SILCL3 (EN 62
061)
Category
Category 4 (EN ISO 13
849-1)
Performance Level
31)
PL e (EN ISO 13
849-1)
T
M
(mission time)
20 years (EN ISO 13
849-1)
PFD
5.8 × 10
–6
PFHd (1/h)
3.8 × 10
–9
SFF
96
%
DC
99
%
Single-channel
input, single-
channel output
Single-channel
input, dual-
channel output
Dual-channel
input, single-
channel output
Dual-channel
input, dual-
channel output
PFD (
⊕
)
2.4 × 10
–5
7.0 × 10
–6
2.3 × 10
–5
5.8 × 10
–6
% of SIL3
2.4
%
0.7
%
2.3
%
0.6
%
PFHd (1/h)
7.3 × 10
–9
3.8 × 10
–9
7.3 × 10
–9
3.8 × 10
–9
% of SIL3
7.3
%
3.8
%
7.3
%
3.8
%
11.1.4
UE410-2RO/UE410-4RO output modules
Minimum
Typical
Maximum
Supply circuit (via UE410-MU)
Power consumption
UE410-4RO
–
–
3.2 W
UE410-2RO
–
–
1.6 W
Input circuit B1, B2
Input voltage
18 V DC
–
30 V DC
Output circuit (13/14, 23/24, 33/34, 43/44)
Number of N/O contacts
UE410-2RO
–
2
–
UE410-4RO
–
4
–
Number of N/C contacts
UE410-2RO
–
1
–
UE410-4RO
–
2
–
31)
For detailed information on the safety design of your machine/system, please contact your local SICK
representative.
Tab. 44: PFD and PFHd
values for UE410-8DI
Tab. 45: Data sheet
UE410-2RO/UE410-4R0