Operating instructions
Chapter
11
Flexi Classic
8011509/YPP0/2015-10-26
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
103
Subject to change without notice
Technical specifications
Minimum
Typical
Maximum
Load capacity
–
–
500 nF
Cable length (single, Ø 1.5 mm²)
–
–
100 m
Local response time cut-off path
(I1/I2)
–
–
29 ms
Local response time cut-off path
(I3/I4)
23)
program 2, 3, 4 and 5
–
–
29 ms
Local response time cut-off path
(I3/I4)
23)
program 6, 7
–
–
13 ms
Local response time cut-off path
(I4)
23)
program 8, 9 with tested
electro-sensitive protective device
cat. 4 (e.g. L41)
–
–
56 ms
Local response time
on
connection of Flexi Loop
–
–
56 ms
Global emergency stop circuit (O
P
-I
N
, O
N
-I
P
)
Cable length O
X
to I
X
–
–
100 m
Cable length all stations, global
emergency stop function
–
–
1000 m
Number of stations, global
emergency stop function
–
–
32
Global response time I
X
to O
X
–
–
40 ms
Global power-up delay I
X
–
80 ms
120 ms
General system data
Weight (without packaging)
–
0.18 kg
–
Electrical safety
Class III
Interference resistance
EN 61
000-6-2
Radiated emission
EN 61
000-6-4
Operating data
Ambient operating temperature
(UL/CSA: ambient temperature)
–25 °C
–
55 °C
Storage temperature
–25 °C
–
70 °C
Air humidity
10
% to 95
%, non-dewing
Climatic conditions
EN 61
131-2
Mechanical strength
Vibration
EN 61
131-2
Vibration resistance
5-500 Hz/5 grms (EN 60
068-2-64)
23)
Time without sensor, in addition the data for the sensors connected apply.
24)
Response time not including Flexi Loop and not including sensor. Also take into account the response times of
Flexi Loop and the sensors connected.