Technical specifications
11.1.2
UE410-GU module
Minimum
Typical
Maximum
Supply circuit (A1, A2)
Supply voltage U
B
19.2 V DC
24 V DC
30 V DC
Type of supply voltage
PELV or SELV
The current from the power supply that supplies the
main module must be limited externally to max. 6 A
— either by the power supply itself or by a fuse.
Residual ripple U
ss
–
–
3 V
Power consumption
–
–
3 W
Maximum switch-on time
–
–
60 s
Short-circuit protection
4 A gG with tripping characteristic B or C
Input circuit (I1-I4, I
P
, I5, I6, I
N
)
Number of inputs
–
–
8
Input voltage (high)
13 V DC
–
30 V DC
Input voltage (low)
–5 V DC
–
5 V DC
Input current (high)
2.4 mA
3 mA
3.8 mA
Input current (low)
–2.5 mA
–
2.1 mA
Input capacitance
9 nF
10 nF
11 nF
Minimum switch-off time
(I1/I2) 20 ms
–
–
Minimum switch-off time
20)
(I3/I4)
program 6, 7
7 ms
–
–
Minimum switch-off time
20)
(I3/I4)
program 2, 3, 4, 5, 8, 9
20 ms
–
–
Maximum interruption time for the
input signal without switching the
output (Q1)
–
–
1 ms
Local power-up delay (I1-I4)
–
–
70 ms
Local reset time
–
–
124 ms
Teach-in time of ENTER button
(during power-up)
–
–
3 s
Duration of actuation of the reset
button (I6)
50 ms
–
5 s
20)
Time without sensor, in addition the data for the sensors connected apply.
Tab. 41: Data sheet
UE410-GU