72
EuroFID · Operating Instructions · 8011094 V2.3 · © SICK AG
Terminal Modules (Accessory)
7.2
Terminal module 2
7.2.1
Functions
Terminal module 2 extends the signal connections by the following functions:
●
The switching outputs of the operating unit are available as potential-free relay
switching contacts
●
Latching of the alarm signals, independently of the operating unit (
deactivation of the alarm signals by means of connected pushbuttons
●
Safety circuits for alarm signals
●
Additional control input for the “Maintenance” status (e.g. for a key switch)
●
Additional signal outputs for the device status and alarm (e.g. for signal lamps)
●
Test function for connected signal lamps (by means of connected buttons)
●
Analog inputs can be equipped for the signal range 0/4 … 20 mA (instead of 0 … 10 V)
●
Plug connector with its own switching inputs and outputs for connection of a control
and indicator panel
●
Additional terminal strip (X10) for the connection of additional devices (e.g. recording
instrument)
7.2.2
Technical design
●
Mechanically the terminal module is a plug module for standard mounting rails in
circuit cabinets (dimensions
).
●
Terminal module 2 requires an external power supply (24 VDC/17 W).
Fig. 23
Terminal module 2
All control inputs of the terminal module are directly connected to the control
inputs of the operating unit (malfunction of the gas supply, maintenance block,
calibration block).
●
Fuse: 1 A MT
●
Circuit diagram
X2
X30
X10
X1
X20
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9 10 11 12 13 14
+24V
J5
J4
J40
Option Meas
extFail
R1
R2
X21
1
2
3
4
5
6
7
8
9 10 11 12 13 14
J3
J1
J2
Analog
Input 2
Ch. 2
Ch. 3
Ch. 4
J8
J6
J7
Main...
Pr
elal...
Alar
m...
J60
GND
24 VDC
Summary of Contents for EuroFID
Page 10: ...Contents 10 EuroFID Operating Instructions 8011094 V2 3 SICK AG ...
Page 18: ...18 EuroFID Operating Instructions 8011094 V2 3 SICK AG Important Information ...
Page 80: ...80 EuroFID Operating Instructions 8011094 V2 3 SICK AG Start up ...
Page 88: ...88 EuroFID Operating Instructions 8011094 V2 3 SICK AG Operation General ...
Page 100: ...100 EuroFID Operating Instructions 8011094 V2 3 SICK AG Main Menu Functions ...
Page 144: ...144 EuroFID Operating Instructions 8011094 V2 3 SICK AG Maintenance Sub menu Functions ...
Page 154: ...154 EuroFID Operating Instructions 8011094 V2 3 SICK AG Calibration ...
Page 158: ...158 EuroFID Operating Instructions 8011094 V2 3 SICK AG Shutdown ...
Page 182: ...182 EuroFID Operating Instructions 8011094 V2 3 SICK AG Clearing Malfunctions ...