Technical specifications
Minimum
Typical
Maximum
Alignment laser
Class 1 in accordance with IEC 60 825
@
1:2007 and
21 CFR 1040.10 and 1040.11 except for
deviations pursuant to Laser Notice No. 50, June
24, 2007, optical output power 390 µW CW
typical
= 650 nm
Weight, type dependent
Depending on protective field height (see page 63)
Receiver unit
Switching outputs (OSSDs)
Dual-channel, PNP semiconductor, short-circuit
protected
, cross-circuit monitored
Response time
Switch off time
100 ms
Switching voltage
HIGH
(active, U
eff
)
U
V
– 2.25 V DC
24 V DC
U
V
Switching voltage
16)
LOW
(inactive)
0 V
0 V
2.0 V DC
Switching current
0 mA
500 mA
Leakage current
0.25 mA
Load capacity
2.2
µ
F
Switching sequence
Depending on load inductance
Load inductance
2.2 H
Test pulse data
Test pulse width
120
µ
s
150
µ
s
300
µ
s
Test pulse rate
3
1
/s
5
1
/s
10
1
/s
Permissible line resistance
between device and load
2.5
Supply lead
1
Power consumption
14)
Applies to the voltage range between –30 V DC and +30 V DC.
15)
Switch off time represents the minimum amount of time that the OSSDs will be switched off when the C4000
Select transitions to an inactive (low) (i.e. red) state.
16)
As per IEC 61 131
@
2.
17)
On the device plug.
18)
In the case of a fault (0 V cable open circuit) the max. leakage current flows in the OSSD cable. The down-
stream controller must detect this status as LOW. A FPLC (Fail-safe Programmable Logic Controller) must be
able to identify this status.
19)
The maximum rated load inductance is higher with lower switching sequence.
20)
When active, the outputs are tested cyclically (brief LOW). When selecting the downstream controllers, make
sure that the test pulses do not result in deactivation when using the above parameters.
21)
Make sure to limit the individual line core resistance to the downstream controller to this value to ensure that
a short-circuit between the outputs is safely detected. (Also note EN 60 204 Electrical Machine Equipment,
Part 1: General Requirements.)