INFORMATION!  For  some  types  of  plants,  the  sequences  depend  on  the  Software  and  Hardware 

configuration of the plant during the installation activity. 
 

 

• 

AUTO 

(Engine Started/Stopped automatically): In this mode, according to the operating conditions, the device 

starts the genset (

START

), manages the 

GCB

 closing if needed, and checks the electrical measurements.  

 

WARNING! 

The STOP 

button, causes the stop of the Generator if running and the activation 

of a lockout, unless configured otherwise.   
 

According to the configuration set, if the Genset operation is no longer required, the device carries out the 
power discharge and/or open the 

GCB

 and carries out the engine cooling for the time set. Once the cooling is 

over, it stops the engine (

STOP

).  

WARNING!

 

Assigning an incorrect value to one or more parameters can cause malfunctioning or 

damage to things and/or people. The parameters changes must be carried out only by skilled personnel. 
Parameters may be password protected (see par. Access codes).

 

In order to adjust the parameters, it is necessary to enter the 

PROGRAMMING

 menu (page 

P.XX

).   

The access to the parameters programming mode can be protected by 

3

 or 

4

 different 

PASSWORD

 levels 

(it 

depends on the device)

, which are listed in order of priority. 

1.  SICES Password (Only for Parallel plants)  
2.  Maker Password 
3.  System Password 
4.  User Password 

If the password is lost, you can reconfigure it using a higher level password. Contact the technical support if 
the “MAKER” password is lost. 

Enter the authentication password on page 

1.1.1

.

 Authentication.

 To access, enter the various menus and 

submenus following the path: 

PROGRAMMING

1. SYSTEM

1.1 Safety 

1.1.1. 

Authentication The (

000-Access 

Code

) page of the 

Safety 1/02

 menu requires the setting of the access code if one or more passwords have been 

assigned. The password is not assigned if equal to 0.The set access code remains in the memory for about 10 
minutes after programming has been completed. After that, it must be entered again to access the programming 
mode.

 

Parameters settings 

In the 

PROGRAMMING

 page, enter the submenus with the 

ENTER

 button. Use the 

UP

 and 

DOWN

 buttons to select 

the submenu required and the 

ENTER

 button to access it. Select the submenu or the parameter required with the 

UP

 

and 

DOWN

 buttons. By pressing 

ENTER

, you enable the adjustment of the parameter value that is signalled by the 

square brackets 

[..]

 flashing. Use the 

UP

 and 

DOWN

 buttons to change the  value and press 

ENTER

 to confirm or 

EXIT 

to cancel the change. If the square brackets are replaced by the symbols 

< >

, it means that the change of the 

parameter value is not allowed. This can happen for lack of Password authorizations or in case you are trying to change 
a parameter in a mode that is not allowed: some parameters can be changed only in 

PROGRAM 

– OFF/RESET

 mode. 

Press 

EXIT 

to exit the programming menu.

 

Language selection  

To select a different language from the one set, view the screen

 S.03 (BOARD STATUS)

 using the navigation buttons. 

To change the 

LANGUAGE

 press 

ENTER

: the square brackets 

[..]

 will flash. Use the 

UP

 and 

DOWN

 buttons to check 

the languages available, then press 

ENTER 

to confirm. 

EXIT

 cancels the change. 

Parameters for protections and alarms 

The protections and the alarms  are usually  adjustable by means  of proper  variables. Usually, the intervention time 
related to the protection can be configured too.  

By setting the acquisition time at 0 (zero), the protection is deactivated.

   

 

Parameter description 

U.M.  Value 

 

Parameter description 

U.M.  Value 

 

SYSTEM 

 

 

P.0107 

Primary of C.T. auxiliary current 

P. 0001  Maker password 

 

P.0139 

Secondary of C.T. auxiliary current 

P. 0002  System password 

 

P.0109 

Transformer type for aux. current 

 

P. 0003  User password 

 

P.0130 

Usage of auxiliary current 

 

P. 0802  Plant type 

 

P.0317 

Currents unbalance threshold 

5.0 

 

 

MAINS

 

 

 

P.0318 

Currents unbalance delay 